Preparation for wiring 2.5, Figure 2-1, 1 wiring guidelines – West Control Solutions MRC 7000 Recorder Manual User Manual

Page 8

Advertising
background image

8

FIGURE 2-1

Preparation for Wiring 2.5

2.5.1 WIRING GUIDELINES

Electrical noise is a phenomenon typical of industrial environments. The following are guide-
lines that must be followed to minimize the effect of noise upon any instrumentation.

2.5.1.1 INSTALLATION CONSIDERATIONS

Listed below are some of the common sources of electrical noise in the industrial environment:
• Ignition Transformers
• Arc Welders
• Mechanical contact relay(s)
• Solenoids

Before using any instrument near the devices listed, the instructions below should be followed:

1. If the instrument is to be mounted in the same panel as any of the listed devices, separate
them by the largest distance possible. For maximum electrical noise reduction, the noise
generating devices should be mounted in a separate enclosure.

(320.7 mm)
(190.5 mm)

(342.5 mm)

( 354 mm)

9

32 DIA.(7.1mm)

Panel cut-out for flush mounting

15 1

8

(384.2 mm)

2 1

2

(64 mm)

WIDTH OF COVER

4

16

9 1 m

16

5 mm)

EC1

12

5

8

7 1

2

13

1

2

13 15

16

(65.9 mm)

219

32

2.5"

63.5mm

Advertising