2 parameters 19, Parameter setting 19, 3 input scaling inp.1 – West Control Solutions TB 40-1 Temperature Monitor User Manual

Page 19: Parameter setting level, Inp.1

Advertising
background image

5.3 Input scaling

InP.1

When using current or voltage signals as input variables for

InP.1 scaling of

input and display values at parameter setting level is required. Specification of
the input value for lower and higher scaling point is in the relevant electrical unit
(mA/ V).

g

Parameters

InL.1 , OuL.1, InH.1 and OuH.1 are only visible if

ConF / InP.1 / Corr = 3 is chosen.

In addition to these settings,

InL.1 and InH.1 can be adjusted in the range

(0...20mA / 0...10V) determined by selection of

S.tYP .

a

For using the predetermined scaling with thermocouple and resistance
thermometer (Pt100), the settings for

InL.1 and OuL.1 and for InH.1 and

OuH.1 must have the same value.

g

Input scaling changes at calibration level (r page 20) are displayed by input
scaling at parameter setting level. After calibration reset (

OFF), the scaling

parameters are reset to default.

Parameter setting level

TB40-1

19

Input scaling

InP.1

mA/V

phys.

quantity

mA / V

phys. quantity

OuH.x

OuL.x

InH.x

InL.x

S.tYP

Input signal

InL.1

OuL.1

InH.1

OuH.1

30

(0...20mA)

0 … 20 mA

0

any

20

any

4 … 20 mA

4

any

20

any

40

(0...10V)

0 … 10 V

0

any

10

any

2 … 10 V

2

any

10

any