9 technical data 26, Current signal measuring range 26, Technical data 26 – West Control Solutions TB 40-1 Temperature Monitor User Manual

Page 26: Power supply 26, Resistance thermometer measuring range 26, Thermocouple measuring range 26, Voltage signal measuring range 26, Technical data, Ac supply, Universal supply 24 v uc

Advertising
background image

AC SUPPLY

Voltage:

90...250 V AC

Frequency:

48...62 Hz

Power consumption

approx. 7.3 VA

UNIVERSAL SUPPLY 24 V UC

AC voltage:

20,4...26,4 V AC

Frequency:

48...62 Hz

DC voltage:

18...31 V DC

Power consumption:

approx.. 7.3 VA

BEHAVIOUR WITH POWER FAILURE

Configuration, parameters and adjusted
set-points, control mode:
Non-volatile storage in EEPROM

BLUEPORT FRONT INTERFACE

Connection of PC via PC adapter (see
"Accessory equipment"). The BlueControl
software is used to configure, set parameters
and operate the TB40-1.

ENVIRONMENTAL CONDITIONS

Protection modes

Front panel:

IP 65 (NEMA 4X)

Housing:

IP 20

Terminals:

IP 00

Permissible temperatures

For specified accuracy:

0...60°C

Warm-up time:

15 minutes

For operation:

-20...65°C

For storage:

-40...70°C

Humidity

75% yearly average, no condensation

Altitude

To 2000 m above sea level

Shock and vibration

Vibration test Fc (DIN 68-2-6)

Frequency:

10...150 Hz

Unit in operation:

1g or 0,075 mm

Unit not in operation:

2g or 0,15 mm

Shock test Ea (DIN IEC 68-2-27)

Shock:

15g

Duration:

11ms

Electromagnetic compatibility

Complies with EN 61 326-1
(for continuous, non-attended operation)

GENERAL

Housing

Material:

Makrolon 9415 flame-retardant

Flammability class:

UL 94 VO, self-extinguishing

Plug-in module, inserted from the front

Safety test

Complies with EN 61010-1 (VDE 0411-1):
Overvoltage category II
Contamination class 2
Working voltage range 300 V
Protection class II

Certifications

Type tested to EN 14597
With certified sensors applicable for:

w

Heat generating plants with outflow
temperatures up to 120°C to DIN 4751

w

Hot-water plants with outflow temperatures
above 110°C to DIN 4752

w

Thermal transfer plants with organic transfer
media to DIN 4754

w

O

il-heated plants to DIN 4755

cULus-certification

(Type 1, indoor use)
File: E 208286

Electrical connections

w

Flat-pin connectors 1 x 6,3 mm or
2 x 2,8 mm to DIN 46 244

Mounting

Panel mounting with two fixing clamps at
top/bottom or right/left. High-density mounting
possible

Mounting position:

uncritical

Weight:

0,27kg

Accessories delivered with the unit

Operating manual
Fixing clamps

Technical data

26

TB40-1

Advertising