Technical data

INPUTS

PROCESS VALUE INPUT INP1

Resolution:

> 14 bits

Decimal point:

0 to 3 digits behind the decimal point

Dig. input filter:

adjustable 0,000...9999 s

Scanning cycle:

100 ms

Measured value
correction:

2-point or offset correction

Thermocouples

r

Table 1 (page 27 )

Input resistance:

³ 1 MW

Effect of source resistance:

1

mV/W

Cold-junction compensation

Maximal additional error:

± 0,5 K

Sensor break monitoring

Sensor current:

£1 mA

Configurable output action

Resistance thermometer

r

Table 2 (page 27 )

Connection:

2 or 3-wire

Lead resistance:

max. 30 Ohm

Input circuit monitor:

break and short circuit

Special measuring range
BlueControl (engineering tool) can be used to
match the input to sensor KTY 11-6
(characteristic is stored in the controller).

Physical measuring range:

0...4500 Ohm

Linearization segments

16

Current and voltage signals

r

Table 3 (page 27 )

Span start, end of span: anywhere within measuring range
Scaling:

selectable -1999...9999

Linearization:

16 segments, adaptable with
BlueControl

Decimal point:

adjustable

Input circuit monitor:

12,5% below span start (2mA, 1V)

CONTROL INPUT DI1

Configurable as switch or push-button!
Connection of a potential-free contact suitable
for switching “dry” circuits.

Switched voltage:

2,5 V

Current:

50

mA

GALVANIC ISOLATION

Safety isolation
Function isolation

OUTPUTS

OUTPUT OUT LC

Function:
Interruption of the power supply if the set limit
is exceeded or fallen short.

Contact type:

potential-free changeover contact

Max.contact rating:

500 VA, 250 V, 2A at 48...62 Hz,
resistive load

Min. contact rating:

5V, 10 mA AC/DC

Operating life (electr.):

600.000 duty cycles with max.
contact rating

OUTPUTS OUT1, OUT2

Function:
Additional alarms with MAX, MIN or MAX+MIN
monitoring with adjustable hysteresis.
Monitored signals:

w

process value (absolut)

w

difference to the limit (relative)

w

sensor break / short circuit

According to the input type, the input signal is
monitored to sensor break, polarity error and
short circuit

Contact type:

2 NO contacts with common
connection

Max. contact rating:

500 VA, 250 V, 2A at 48...62 Hz,
resistive load

Min. contact rating:

6V, 1 mA DC

Operating life (electr.): 800.000 duty cycles with max. rating

Note:
If the relays OUT1...OUT LC operate external
contactors, these must be fitted with RC
snubber circuits to manufacturer specifications
to prevent excessive switch-off voltage peaks.

POWER SUPPLY

Dependent of order

Technical data

TB40-1

25

Power supply connections Process value input INP1

Digital input di1

Relay outputs OUT 1,2
Relay output OUTLC