4 standard protocol 11, 1 code table 11, Standard protocol 11 – West Control Solutions KS 800 ISO1745 Interface Manual User Manual

Page 11: System identification number 11, Standard protocol, Code table, 4standard protocol

Advertising
background image

4

Standard protocol

The KS800 standard protocol version represents instrument-specific standard data.

4.1

CODE table

Code

Description

R/W

Type

Range

Description

Rem.

18

System ident

R

SYS16

System identification

A

80

Block 81... 83

R

Block

81

Write Error

R

INT

0, 100 ... 127 Error of last write access

B

82

Write Error Position R

INT

0 ... 99

Position of last write access error

83

Read Error

R

INT

0, 100 ... 127 Error of last read access

Bem. A Instrument data

System dentifiction number (code 18)
For instrument identification, instrument type and software code number

can be read via code 18. The datum is composed of the following

sections:
Instrument type: (30 =KS800)

SW code number: (the last 8 digits)

Instrument version: 7th to 10th digit of 12NC (4 digits)

Bem. B Diagnosis access: block 8x

For test purposes, an additional debug access which signals errors of the last write or read access is available.

Presently, reading is possible for:

w

error number of last write access; 0 = no error

w

position of the faulty datum during the last write access;

0 = no error or error in address

1 = first datum is faulty (also with single accesses)

n = nth datum is faulty (with block accesses)

w

error number of last read access; 0 = no error

An independent memory for error messages is available for each interface COM1 and COM2. Presently, the

following error messages are defined:

Err. no.

Description

Error name

101

unspecified error

ERR_UNSPECIFIED

102

read not permitted

ERR_RD_NOTALLOWED

103

write not defined

ERR_WR_NOTALLOWED

104

local operation / no write access

ERR_LOCOPERAT

105

non-defined key code

ERR_KEYIDENT

106

range overflow function block no.

ERR_FB_OVERFL

107

range overflow function no.

ERR_FCT_OVERFL

108

write or range overflow

ERR_WR_RANGE_OV

109

char is not a digit

ERR_NODIGIT

110

no ‘\0’ found in the correct position

ERR_ENDDELIMITER

111

no ‘=’ in the correct position

ERR_NO_EQUALSIGN

112

faulty ST1 format (status)

ERR_NO_ST1FORMAT

113

no ‘,’ in the correct position

ERR_NO_COMMA

114

byte range overflow

ERR_BYTE_OVERFL

115

number of digits exceeded

ERR_DIGIT_OVERFL

116

range 9999 exceeded

ERR_RG9999_OVERFL

117

undefined protocol type

ERR_UNDEF_PRTCTYPE

118

undefined parameter reference

ERR_UNDEF_PARAMREF

119

undefined decimal point

ERR_UNDEF_DECPNT

Standard protocol

11

9499 040 49411

3 0 , 1 2 3 4 5 6 7 8 , 1 2 3 4

Advertising