West Control Solutions KS 800 ISO1745 Interface Manual User Manual

Page 25

Advertising
background image

Output variable

Output variable processing

(function no.:4)

Code Des.

R/W Type

Description

Range

Rem.

30

Block

R

Block

Block access (31, 35)

31

dYman R/W BCD

Difference output variable

-210..210

32

Yman

R/W BCD

Absolute output variable

-105..105

33

Yinc

R/W INT

Increment. output variable

0, 1

34

Ydec

R/W INT

Decrement. output variable

0, 1

35

Ygrw_ls R/W INT

Speed for incr./decr. output variable offset

0, 1

Tuning

Self-tuning(Function no.:5)

Code Des.

R/W Type

Description

Range

Rem.

00

Block

R

Block Block access (1, 3)

1

State_Tune1

R

ST1

Status Tuning

C

3

ParNeff

R

INT

Eff. parameter set number

0...1

30

Block

R

Block Block access (31...39)

31

ParNr

R/W INT

Parameter set number effective

0 .. 1

32

Tu1

R

BCD

Delay time heating

0...9999 s

33

Vmax1

R

BCD

Rate of increase heating

0,000...9,999 %/s

34

Kp1

R

BCD

Process gain heating

0,000...9,999

35

MSG1

R

INT

Error code of self-tuning heating

0...8

36

Tu2

R

BCD

Delay time cooling

0...9999 s

37

Vmax2

R

BCD

Rate of increase cooling

0,000...9,999 %/s

38

Kp2

R

BCD

Process gain cooling

0,000...9,999

39

MSG2

R

INT

Error code of self-tuning cooling

0...8

Bem. C Status 1 Tuning ‘State_Tune1’

MSB

LSB

D7

D6

D5

D4

D3

D2

D1

D0

Bit no.

Name

Allocation

Status ‘0’

Status ‘1’

D0

OStab

Process at rest

no

yes

D1

Orun

Self-tuning mode

off

on

D2

Oerr

Self-tuning result

Ok

error

D3...D5 ‘0’

Always ‘0’

D6

‘1’

Always ‘1’

D7

Parity

Parameter a. configuration data

General

(Function no.: 0)

Code

Des.

R/W

Type

Description

Range

Rem.

B3

71 C100

R/W

INT

CFunc: controller function

CType: controller type

WFunc:set-point function

(T,H)

(Z)

(E)

0..xxyz

72 C101

R/W

INT

CMode:controller output action

CDiff: x/x-w differentiation

CFail: behaviour with sensor fail

CAnf: start-up circuit

(T)

(H)

(Z)

(E)

0..wxyz

73 C700

R/W

INT

OMode: self-tuning mode

OCond: process at rest

OGrp: allocation group self-tuning

OCntr: controlled adapt. mode

(T)

(H)

(Z)

(E)

0..wxyz

74 C180

R/W

INT

SWext: source for Wext

(T) 0..x000

Function block protocol

25

9499 040 49411