3 message structure in function block protocol 30, 1 instrument 30, 2 input 30 – West Control Solutions KS 800 ISO1745 Interface Manual User Manual

Page 30: 3 contr 30, 4 alarm 30, 2 input, 3 contr, 4 alarm, Message structure in function block protocol 6.3.1

Advertising
background image

6.3

Message structure in function block protocol

6.3.1

INSTRUMENT

Message structure for function ‘General’

Block access to configuration data

max. eff. length: 41 bytes

STX B3 , 0 , 0 = 0 , 0 , 5 , C900 , Adr1 , C904 , C902 , Adr2

ETX

BCC

Message structure for function ‘I/O connection’

Block access to configuration data

max. eff. length: 43 bytes

STX B3 , 0 , 2 = 0 , 1 , HC100 , 4 , C500 , C530 , C551 , HCcycl

ETX

BCC

6.3.2

INPUT

Message structure for function ‘ME/V1’

Block access to parameter data

max. eff. length: 44 bytes

STX B2 , 6x , 1 = 112

, 4 , X1in

, X1out

, X2in

, X2out

, 0 ETX BCC

Block access to configuration data

max. eff. length: 66 bytes

STX B3 , 6x , 1 = 112 , 5 , X0 , X100 , XFail , Tfm , Tkref , 3 , C200 , C205 , C190 ETX BCC

6.3.3

CONTR

Message structure for function ‘General’

Block access to configuration data

max. eff. length: 36 bytes

STX B3 , 5x , 0

= 91 , 0 ,

4

,

C100 ,

C101 ,

C700 ,

C180 ETX BCC

Message structure for function ‘Set-point’

Block access to parameter data

max. eff. length: 56 bytes

STX B2 , 5x , 1

= 91 , 6 ,

W0

,

W100 ,

W2

,

Grw+ ,

Grw-

,

Grw2 ,

0

ETX

BCC

Message structure for function ‘Algo’

Block access to parameter data

max. eff. length: 72 bytes

STX B2 , 5x , 3 = 91 , 8

,

Xsh , Tpuls ,

Tm , Xsd

1

,

LW

, Xsd

2

, Xsh

1

,

Xsh

2

, 0 ETX

BCC

Message structure for function ‘Output variable’

Block access to parameter data

max. eff. length: 51 bytes

STX B2 , 5x , 4 = 91 , 5 ,

Ymin , Ymax ,

Y0

,

Yh

, LYh , 0 ETX

BCC

Message structure for function ‘Tuning’

Block access to parameter data

max. eff. length: 49 bytes

STX B2 , 5x , 5 = 91 , 4 , YOptm , dYopt , OXsd , Trig1 , 1 , POpt ETX BCC

Message structure for function ‘Paramset x’

Block access to parameter data

max. eff. length: 72 bytes

STX B2 , 5x , <6, 7> = 91 ,

8 , Xp1 , Tn1 , Tv1 ,

T1 , Xp2 , Tn2 , Tv2 ,

T2 , 0

ETX

BCC

Message structure for function ‘Start-up circuit’

Block access to parameter data

max. eff. length: 37 bytes

STX B2 , 5x , 10

= 91 , 3 ,

Ya

,

Wa

,

Tpa

,

0

ETX

BCC

6.3.4

ALARM

Message structure for function ‘General ‘

Block access to parameter data

max. eff. länge: 58 bytes

STX B2 , 7x , 0 = 46 , 6 , LimL , LimH , xsd_1 , LimLL , LimHH , LimHC ETX BCC

Block access to configuration data

max. eff. length: 36 bytes

STX B3 , 7x , 0 = 46 , 0 , 2 ,

C600

,

C601

ETX

BCC

Examples

9499 040 49411

30

990924

Advertising