15

EcoChill

Chiller

Technical Manual 7300221 V1.1.0_02/2013

COOLING

020°

025°

030°

040°

050°

070°

080°

090°

100°

150°

200°

Cooling capacity

kW

5.7

6.2

7.5

9.6

13.4

16.5

20.5

22.3

26.6

33.0

43.0

Total input power

(°)

kW

1.84

2.00

2.46

3.25

4.03

4.88

6.33

6.63

8.4

10.0

13.7

A/P

kW

1.99

2.15

2.61

3.40

4.30

5.15

6.60

6.90

9.2

11.5

15.2

Q/N

kW

N.A.

N.A.

N.A.

N.A.

4.48

5.33

6.78

7.08

9.4

11.3

15.0

Evaporator water flow rate

l/h

980

1070

1290

1650

2310

2840

3530

3840

4580

5680

7400

Evaporator pressure drops

kPa

20.0

20.0

20.0

21.0

21.0

21.0

26.0

25.0

43.0

39.0

32.0

ENERGY EFFICIENCIES

EER

W/W

3.10

3.10

3.05

2.95

3.33

3.38

3.24

3.36

3.16

3.30

3.14

ESEER

3.72

3.72

3.66

3.54

3.99

4.06

3.88

4.03

4.14

4.25

4.12

ELECTRICAL DATA
Total input current(without circu-

lation pump)

(°)

400V A

3.7

4.2

4.70

6.2

8.7

9.7

12.2

12.8

16.7

18.8

25.7

230V

9.4

10.0

13.0

16.3

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

Total input current(with circula-

tion pump)

A/P

400V A

4.7

5.2

5.70

7.2

10.7

11.7

14.2

14.8

17.9

20.8

27.7

230V

10.4

11.0

14.0

17.3

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

Q/N 400V

N.A.

N.A.

N.A.

N.A.

11.4

12.4

14.9

15.5

18.7

21.4

28.3

Maximum current (FLA)(without

circulation pump)

(°)

400V A

6

6

6.7

8.7

11.3

13.5

16.3

17.3

22.0

26.0

34.0

230V

16.5

16.5

19.7

23.7

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

Maximum current (FLA)(with

circulation pump)

A/P

400V

A

7

7

7.7

9.7

13.3

15.5

18.3

19.3

23.4

28.8

36.8

230V

17.5

17.5

20.7

24.7

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

Q/N 400V

N.A.

N.A.

N.A.

N.A.

14.0

16.2

19.0

20.0

24.8

29.5

37.5

Peak current (LRA)(without

circulation pump)

(°)

400V A

26.5

32.5

35.7

48.7

65.3

75.3

102.3

96.3

76.0

87.0

117.0

230V

59.5

62.5

83.7

98.7

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

Peak current (LRA)(with

circulation pump)

A/P

400V

A

27.5

33.5

36.7

49.7

67.3

77.3

104.3

98.3

77.4

89.8

119.8

230V

60.5

63.5

84.7

99.7

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

400V

N.A.

N.A.

N.A.

N.A.

68.0

78.0

105.0

99.0

78.8

90.5

120.5

REFRIGERANT CHARGE
R410A

(°) - P

Kg

1.250

1.300

1.560

2.00

3.480 3.790

3.730

4.700

8.0

11.5

12.0

A

1.300

1.300

1.560

2.00

3.415 3.740

3.730

4.700

8.0

11.5

12.0

COMPRESSORS (SCROLL)

Number/circuit

1/1

1/1

1/1

1/1

1/1

1/1

1/1

1/1

2/1

2/1

2/1

Compressors sump heater

n°xW

1x70

1x70

1x70

1x70

1x35

1x35

1x35

1x65

2X35

2X35

2X65

Capacity controls

%

0-100

0-100

0-100 0-100 0-100 0-100 0-100

0-100 0-50-100 0-50-100 0-50-100

FANS (AXIAL)

Number

1

1

1

1

2

2

2

2

2

2

2

Air flow rate

mc/h

2500

2500

3500

3500

7200

7200

7300

7200

13200

12000

12000

Input power

kW

0.085

0.085

0.14

0.14

0.28

0.28

0.28

0.28

0.6

0.6

0.6

Input current

A

0.45

0.45

0.66

0.66

1.32

1.32

1.32

1.32

2.6

2.6

2.6

EVAPORATOR (PLATES)

Number

1

1

1

1

1

1

1

1

1

1

1

CIRCULATION PUMP

Input power

kW

0.15

0.15

0.15

0.15

0.27

0.27

0.27

0.27

0.6

1.0

1.0

Input current

A

1.04

1.04

1.04

1.04

1.95

1.95

1.95

1.95

1.2

2.0

2.0

Avaliable pump head

kPa

60.0

60.0

59.0

55.0

82.0

80.0

69.0

66.0

84

115

90

LARGER CIRCULATION PUMP

Input power

kW

N.A.

N.A.

N.A.

N.A.

0.45

0.45

0.45

0.45

1

1.3

1.3

Input current

A

N.A.

N.A.

N.A.

N.A.

2.7

2.7

2.7

2.7

2

2.6

2.6

Avaliable pump head

kPa

N.A.

N.A.

N.A.

N.A.

160

158

144

140

STORAGE TANK

Water storage

l

25

25

35

35

75

75

75

75

100

100

100

HYDRAULIC CONNECTIONS

Inlet for water circulation

Ø

1"¼

1"¼

1"¼

1"¼

1"¼

1"¼

1"¼

1"¼

1"¼

1"¼

1"¼

Outlet for water circulation

Ø

1"¼

1"¼

1"¼

1"¼

1"¼

1"¼

1"¼

1"¼

1"¼

1"¼

1"¼

NOISE DATA

Sound power

dB(A)

61.0

61.0

68.0

68.0

69.0

69.0

69.0

68.0

76.0

77.0

78.0

Sound Pressure

dB(A)

30.0

30.0

37.0

37.0

38.0

38.0

38.0

37.0

44.0

45.0

46.0

IN COOLING MODE

- Water inlet temperature

12 °C

- Water outlet temperature

7 °C

- External air temperature

35 °C

- ∆t

5°C

Sound power

Airedale determines sound power values in agreement with

the 9614 Standard, in compliance with that requested by

Eurovent certification.

Sound Pressure

Sound pressure measured in free field conditions with

reflective surface (directivity factor Q=2) at 10 mt distance

from external surface of unit, in compliance with ISO 3744

regulations.

4.