EcoChill

Chiller

Technical Manual 7300221 V1.1.0_02/2013

10. EVAPORATOR

PRESSURE DROPS

AND USEFUL STATIC

PRESSURES

The standard ECLs (without storage

tank and/or pump are supplied with

installed water filters as per standard:

- for ECL 020 - 025 - 030 - 040 filter

is 1"

- For ECL 050- 070 - 080 - 090 - 100

- 150 - 200 filter is 1 ¼"

NOTE

The pressure drops and the static

pressures are calculated in cooling

mode with 10°C water.

The table below states the correction

to apply to the pressure drops

on variation of the average water

temperature.

10.1. STATIC PRESSURES USEFUL

TO THE SYSTEM

For the "A, P, N, Q" versions (with

storage tank and/or pump only).

The static pressures stated here

are at net of the pressure drops of

the heat exchangers, filter, storage

tank. Therefore are to be considered

USEFUL TO SYSTEM.

NOTE

The static pressures are

calculated in cooling mode.

WITH PRESENCE OF

GLYCOL for static pressures useful

to system PLEASE CONTACT

COMPANY.

0

0

1000

20

40

60

80

100

120

140

160

180

200

2000 3000

4000 5000

6000 7000 8000

9000 10000 11000 12000

020

025 030

0

40

050

070

090

080-1

00

150

200

10.1.1. Standard versions pressure drops

Water capacity l/h

10.1.2. Filters pressure drops

0

0

5

10

15

20

25

30

35

1

2

3

4

5

6

7

8

9

10

1“

1“ 1/4

1“ 1/2

Water capacity mc/h

Average water temperature °C

5

10

15

20

30

40

50

Multiplicative coefficients

1.02

1

0.985

0.97

0.95

0.93

0.91

Water flow rate l/h

Water flow rate l/h

0

0

50

75

25

100

125

150

175

200

225

1000

2000

3000

4000

5000

6000

7000

8000

9000

10000

020

025 030 040

050

070

080 090

100

150

200

0

0

50

100

150

200

250

2000

4000

6000

8000

10000 12000

070

050

080

090

100

150

200

kPa

kPa

kPa

kPa

10.1.3. Useful static pressures with storage tank

and/or standard pump, (A - P)

10.1.4. Useful static pressures with storage

tank and/or increased Q VERSION

NOTE

The Q version with increased pump is only available for ECL

050 - 070 - 080 - 090 - 100 - 150 – 200 sizes