12. DESUPERHEATER

The heating capacity obtained by

the desuperheater is attained by

multiplying the nominal value (Pd),

given in table 14.1.2. by a relevant

coefficient (Cd).

The diagrams allow to obtain

the corrective coefficients to use

depending on the temperature of the

external air and the temperature of the

water produced at the desuperheater.

NOTE

The use of the desuperheater

is possible in cooling function;

for heat function it must be

intercepted.

12.1. PRESSURE DROPS

All sized models with desuperheater

have 1 desuperheater.

The features of the desuperheater and

the pressure drop curves are given

below.

For Water Temperature °C values,

different from 50°C, multiply the result

obtained by corrective factor.

35

40

45

50

55

60

65

20°C

25°C

45 °C

40 °C

35 °C

30 °C

0

0.5

1

1.5

2

2.5

3

external air temperature d.b.

Temperature of desuperheater produced water ∆t 5° C

Water flow rate l/h

050

070

080 ч 090

100 ч 200

0

0

10

20

30

40

50

60

70

80

90

500

1000

1500

2000

2500

3000

3500

4000

4500

5000

5500

Cd

Average water temperature °C

30

40

50

60

70

Multiplicative coefficients

1.04 1.02

1

0.98 0.96

TAB.14.1.2

050

070

080

090

100

150

200

Heating capacity available

kW

5.4

6.6

8.2

8.9

13.8

17.1

18.9

Water flow rate

l/h

930

1140

1410

1530

2370

2940

3260

Pressure drop

kPa

8

10

11

13

14

24

30

Nominal value refers to:

air temperature

35 °C

water at desuperheater 45/50 °C

∆t

5°C