24

EcoChill

Chiller

Technical Manual 7300221 V1.1.0_02/2013

External air

temperature (C°)

D.B.

Water Temperature °C

35

40

45

50

Ph

Pe

Ph

Pe

Ph

Pe

Ph

Pe

-10

3.8

1.63

-

-

-

-

-

-

-8

4.0

1.63

3.9

1.76

-

-

-

-

-6

4.2

1.62

4.1

1.76

4.0

1.90

-

-

-4

4.4

1.63

4.3

1.76

4.2

1.90

4.1

2.13

-2

4.6

1.63

4.5

1.76

4.4

1.90

4.2

2.13

0

4.8

1.63

4.7

1.77

4.6

1.90

4.4

2.13

2

5.0

1.63

4.9

1.77

4.8

1.90

4.7

2.13

4

6.0

1.63

5.9

1.77

5.7

1.91

5.6

2.14

6

6.3

1.63

6.2

1.77

6.1

1.91

5.9

2.14

7

6.5

1.64

6.3

1.77

6.2

1.91

6.0

2.14

8

6.6

1.64

6.5

1.77

6.3

1.91

6.2

2.14

10

6.9

1.64

6.7

1.78

6.6

1.91

6.4

2.14

12

7.2

1.64

7.0

1.78

6.8

1.92

6.6

2.14

14

7.5

1.64

7.2

1.78

7.0

1.92

6.8

2.15

16

7.7

1.64

7.5

1.78

7.3

1.92

7.0

2.15

18

8.0

1.64

7.8

1.78

7.5

1.92

7.2

2.15

20

8.3

1.64

8.1

1.78

7.8

1.92

7.5

2.15

External air

temperature (C°)

D.B.

Water Temperature °C

35

40

45

50

Ph

Pe

Ph

Pe

Ph

Pe

Ph

Pe

-10

4.3

1.80

-

-

-

-

-

-

-8

4.6

1.80

4.4

1.96

-

-

-

-

-6

4.8

1.80

4.7

1.96

4.5

2.11

-

-

-4

5.0

1.80

4.9

1.96

4.7

2.11

4.6

2.36

-2

5.2

1.81

5.1

1.96

4.9

2.11

4.8

2.36

0

5.4

1.81

5.3

1.96

5.1

2.11

5.0

2.37

2

5.7

1.81

5.5

1.96

5.4

2.11

5.3

2.37

4

6.7

1.81

6.6

1.96

6.5

2.12

6.3

2.37

6

7.1

1.81

7.0

1.97

6.8

2.12

6.7

2.37

7

7.3

1.81

7.2

1.97

7.0

2.12

6.8

2.37

8

7.5

1.82

7.3

1.97

7.1

2.12

7.0

2.38

10

7.8

1.82

7.6

1.97

7.4

2.12

7.2

2.38

12

8.1

1.82

7.9

1.97

7.7

2.13

7.5

2.38

14

8.4

1.82

8.2

1.98

7.9

2.13

7.7

2.38

16

8.7

1.82

8.5

1.98

8.2

2.13

7.9

2.38

18

9.1

1.82

8.8

1.98

8.5

2.13

8.2

2.38

20

9.4

1.83

9.1

1.98

8.8

2.13

8.4

2.38

IN COOLING MODE

- Water inlet temperature

12 °C

- Water outlet temperature

7 °C

- External air temperature

35 °C

- ∆t

5°C

IN HEATING MODE

- Water inlet temperature

40 °C

- Water outlet temperature

45 °C

- External air temperature

b.s. 7 °C

- ∆t

5°C

Ph Heating capacity (kW)

Pe Input power (kW)

8.

PERFORMANCE IN HEATING MODE MODE

8.1.

ECL 020 H

8.2.

ECL 025 H