EcoChill

Chiller

Technical Manual 7300221 V1.1.0_02/2013

11. STORAGE TANK

The following tables highlight

principle characteristics for hydraulic

circuit components, whilst the graph

on the following page shows relative

static pressures.

11.1. MINIMUM/MAXIMUM SYSTEM

WATER CONTENT

The minimum system water content

recommended for units without

hydronic kit is calculated using

following formula:

Volume = PFN(kW) x 4(l)= litres of

system

PFN: Nominal cooling capacity

That resulting minimum water content

necessary for correct function of

system.

The adjacent table indicates maximum

water capacity in litres of hydraulic

plant, compatible with expansion

vessel supplied as standard IN THE

VERSIONS WITH STORAGE TANK

OR PUMP ONLY. The values shown

in the table refer to three maximum

and minimum water temperatures.

If the effective water content of the

hydraulic plant (including the storage

tank) is greater than that given in the

table at operational conditions, another

dimensioned expansion vessel must be

installed, using thenormal criteria, with

reference to the additional volume of

water.

In the following tables it is possible to

work out the maximum values of the

system also for glycol functioning.

Values are worked out by multiplying

the reference value by the corrective

coefficient.

11.2. EXPANSION VESSEL

CALIBRATION

Standard pre-load pressure value of

expansion vessel when empty is 1.5

bar, maximum value is 6 bar.

Calibration of the vessel must be

regulated using the maximum level

difference (H) of the user (see

diagram) by using the following

formula:

p (calibration) [bar] = H [m] / 10.2 +

0.3.

For example: if level difference (H) is

equal to 20m, the calibration value of

the vessel will be 2.3 bar.

If calibration value obtained from

formula is less than 1.5 bar (that is

for H < 12.25), keep calibration as

standard.

ECL 020-025-030
Hydraulic height

H m 30

25

20

15

≥ 12.25

Calibration of expansion vessel

bar

3.2

2.8

2.3

1.8

1.5

Water content reference values

l (1) 103

121

139

158

168

Water content reference values

l (2) 46

55

63

71

76

ECL 040-050-080-090-100-150-200
Hydraulic height

H m 30

25

20

15

≥ 12.25

Calibration of expansion vessel

bar

3.2

2.8

2.3

1.8

1.5

Water content reference values

l (1) 257

303

348

394

419

Water content reference values

l (2) 116

136

157

177

189

Glycoled

water

Water temp. °C

Corrective

coefficients

Recommended

conditions

max.

min.

10%

40

-2

0.507

(1)

10%

60

-2

0.686

(2)

20%

40

-6

0.434

(1)

20%

60

-6

0.604

(2)

35%

40

-6

0.393

(1)

35%

60

-6

0.555

(2)

Recommended operational conditions:

(1) Cooling: Max water temp. = 40 °C, min water temp. = 4 °C.

(2) Heating (hot air pump): Max water temp. = 60 °C, min water temp. = 4 °C.