Design Features & Information

CONTROL SCHEME
FEATURES

Airedale recognises that all chiller applications are different but fall mainly into 2
application categories; Variable Supply Temperature and Constant Supply Temperature.

The onboard microprocessor has the capability of satisfying either control requirement as
illustrated below. Using the Airedale Variable Supply Temperature control scheme,
energy savings are available when compared with previous schemes and that of the
Constant Supply Temperature application.

Variable Supply Temperature control schemes offer energy savings where the supply
water temperature is not critical to its operation.

Selection of the best application control scheme can be made via a soft switch in the
microprocessor during initial commissioning.

Examples based on Models URAC200D having 6 Stages of Cooling

Variable Supply
Temperature Control

6

7

8

9

10

11

12

13

14

W

A

T

E

R

T

E

M

P

E

R

A

T

U

R

E

°

C

20%

40%

50%

60%

80%

100%

Chiller

Capacity %

Cooling Stage

Sequence

1

2

3

4

5

6

Return Water Temperature

Supply Water Temperature

Compressor Off

Mean Value

Constant Supply
Temperature Control

6

7

8

9

10

11

12

13

14

0

2

4

6

8

10

12

14

Supply Water Temperature

Return Water Temperature

Chiller

Capacity %

Cooling Stage

Sequence

20

40

50%

60

80

100%

1

2

3

4

5

6

WA

TER TEM

PER

A

TUR

E °C

CAUTION

Factory set to Variable Supply Temperature Control unless otherwise stated
at order.

Only when the mode selection has been set can the unit be enabled.