Installation Data

ELECTRICAL

General

As standard the equipment is designed for 400V, 3 phase, 3 wire 50Hz and a
separate permanent 230V, 1 phase, 50Hz supply, to all relevant IEE regulations,
British standards and IEC requirements.

A fused and isolated electrical supply of the appropriate phase, frequency and
voltage should be installed.

The control voltage to the interlocks is 24V. Always size the low voltage interlock
and protection cabling for a maximum voltage drop of 2V.

CAUTION

Wires should be capable of carrying the maximum load current under non-fault
conditions at the stipulated voltage.

Avoid large voltage drops on cable runs, particularly low voltage wiring.

CAUTION

A separately fused, locally isolated, permanent single phase and neutral supply
MUST BE FITTED for the compressor sump heater, evaporator trace heating and
control circuits, FAILURE to do so could INVALIDATE WARRANTY.

INTERCONNECTING WIRING


L1

L2

L3

E

Mains incoming supply 400V/3PH/50Hz

L4

N1

E

Separate Permanent Supply 230V/1PH/50Hz

2

External Trace Heater Connections

N

240V/500W max.

502

(1)

Evaporator Pump Interlock 24VAC

503

504

(1)

Evaporator Pump Water Flow Switch 24VAC

506

502

Unit Remote On/Off 24VAC

505

502

Setback Setpoint Temperature switch

507

502

Remote Pump Interlock 24VAC

522

573

Circuit 1

Volt Free Common Alarm

574

Volt Free Alarm N/O

575

Volt Free Alarm N/C

576

Circuit 2

Volt Free Common Alarm

577

Volt Free Alarm N/O

578

Volt Free Alarm N/C

RX-

RX+

pLan Network Connections

URAC75 - URAC450

GND

CAUTION

(1) MUST be directly wired to the chiller to validate warranty.