37

Technical Manual : Part No 6259485 V1.6.0_07_2014

Condenser Installation Data

UNIT LIFTING

Employ lifting specialists.

Local codes and regulations relating to the lifting of this type of equipment should
be observed.

Use the appropriate spreader bars/lifting slings with the holes/lugs provided.

Lift the unit slowly and evenly.

If the unit is dropped, it should immediately be checked for damage and reported
to Airedale Service.

POSITIONING

B

“A”

x 0.5

“B

x

0.
3

A

1000

4000

800

(1)

1000

“B

x

0.
28

(2)

(1) 1 Row of fans, when 2 rows, allow 1.5m between structure and unit.
(2) Free field, for enclosure allow “B” x 0.5.

The installation position should be selected with the following points in mind:

Position on a stable and even base, levelled to ensure that the compressor
operates correctly.

Levelling should be to +/- 5mm

Observe airflow and maintenance clearances.

Pipework and electrical connections are readily accessible.

Where multiple units are installed, due care should be taken to avoid the
discharge air from each unit adversely affecting other units in the vicinity.

Within a side enclosed installation, the fan MUST be higher than the
enclosing structure.

Ensure there are no obstructions directly above the fans.

Allow free space above the fans to prevent air recirculation.