Operating limits, Glycol data, Ultima ™ remote air cooled chillers – Airedale Ultima Remote Air Cooled 75kW - 450kW User Manual

Page 16: Performance data

Advertising
background image

ULTIMA

™ REMOTE AIR COOLED

Chillers

16

Chillers

Technical Manual : Part No 6259485 V1.6.0_07_2014

Performance Data

All performance data is supplied in accordance with BS EN 14511-1:2013

OPERATING LIMITS

(For 100% Water)


Minimum Ambient Air DB °C

-5°C

Maximum Ambient Air DB °C

Refer to

Capacity Data

Minimum Leaving Water Temperature °C

+5°C

Maximum Return Water Temperature °C

+20°C

1

Temperatures lower than those stated can be obtained with the addition of glycol.

2

For conditions outside those quoted, please refer to Airedale.

GLYCOL DATA

Glycol is recommended when a supply water temperature of +5°C or below is required or
when static water can be exposed to freezing temperatures.

Ethylene Glycol Nominal Correction Factors

Glycol in System / Freezing
Point ºC

10% / -4°C

20% / -9°C

30% / -15°C

40% / -23°C

Cooling Duty

x by

0.98

0.97

0.95

0.93

Input Power

0.99

0.98

0.96

0.95

Water Flow

0.99

1.02

1.04

1.07

Pressure Drop

1.05

1.20

1.38

1.57

Propylene Glycol Nominal Correction Factors

Glycol in System / Freezing
Point ºC

10% / -2°C

20% / -6°C

30% / -12°C

40% / -20°C

Cooling Duty

x by

0.97

0.95

0.91

0.88

Input Power

0.99

0.98

0.96

0.95

Water Flow

0.98

0.97

0.95

0.95

Pressure Drop

1.08

1.17

1.31

1.45