Positioning, Chillers ultima ™ remote air cooled, Installation data – Airedale Ultima Remote Air Cooled 75kW - 450kW User Manual

Page 29

Advertising
background image

Chillers

ULTIMA

™ REMOTE AIR COOLED

Chillers

29

Technical Manual : Part No 6259485 V1.6.0_07_2014

Installation Data

POSITIONING

The installation position should be selected with the following points in mind:

Position on a stable and even base, levelled to ensure that the compressor
operates correctly.

Levelling should be to +/- 5mm

Where vibration transmission to the building structure is possible, fit spring anti-
vibration mounts and flexible water connections.

Observe airflow and maintenance clearances.

Pipework and electrical connections are readily accessible.

Where multiple units are installed, due care should be taken to avoid the
discharge air from each unit adversely affecting other units in the vicinity.

CAUTION

Prior to connecting services, ensure that the equipment is installed and
completely level.


C

A

500

500

Controls

Panel

Inlet /
Outlet

B

Model Size

A

B

C

URAC75

– URAC125

mm

1800

760

760

URAC150

– URAC250 (Ex. 240)

mm

2000

760

760

URAC240

– URAC450 (Ex. 250)

mm

3200

900

900