Ultima ™ remote air cooled chillers, General specification – Airedale Ultima Remote Air Cooled 75kW - 450kW User Manual

Page 24

Advertising
background image

ULTIMA

™ REMOTE AIR COOLED

Chillers

24

Chillers

Technical Manual : Part No 6259485 V1.6.0_07_2014

General Specification

ELECTRICAL DATA

URAC200

URAC225

UWC240

URAC250

UWC270

Unit Data

Nominal Run Amps

(1)

A

101

115

120

129

141

Maximum Start Amps

(2)

A

301

355

298

369

314

Permanent Supply

VAC

230V 1PH 50Hz

Mains Supply

VAC

400V 3PH 50Hz

Rec Permanent Fuse Size

A

16

16

16

16

16

Rec Mains Fuse Size

A

160

160

160

200

200

Max Permanent Incoming Cable
Size

mm²

4 mm² terminals

Max Mains Incoming Cable Size

mm²

70 (direct to MCCB)

Control Circuit

VAC

24V/230VAC

Evaporator

Pad Heater Rating

W

100

100

100

100

100

External Trace Heating

Available (fitted by others)

W

500

500

500

500

500

Compressor - Per Compressor

Quantity

4

2+2

3+3

4

3+3

Motor Rating

kW

14.4

14.4/17.9

10.9/10.9

17.9

10.9/14.4

Nominal Run Amps

(1)

A

25.2

25.2/32.2

20.0/20.0

32.2

20.0/25.2

Crankcase Heater Rating

W

120.0

120.0/150.0

70.0/70.0

150.0

70.0/120.0

Start Amps

(2)

225

225/272

198/198

272

198/225

Type Of Start

Direct on line

OPTIONAL EXTRAS

Power Factor Correction

Nominal Run Amps

(1)

A

90

103

112

115

126

Maximum Start Amps

(2)

A

293

346

288

358

301

Recommended Mains Fuse

A

125

160

125

160

160

Compressor Nominal Run
Amps - Per Compressor

A

22.5

22.5/28.8

17.9/17.9

28.8

17.9/22.5

Electronic Soft-Start

Nominal Run Amps

(1)

A

101

115

120

129

141

Maximum Start Amps

(2)

A

211

246

219

260

234

Recommended Mains Fuse

A

160

160

160

200

200

(1)

Based at 12/7°C water and 45°C dew point

(2)

Starting amps refers to the direct on line connections.