Installation Data

UNIT LIFTING

Employ lifting specialists.

Local codes and regulations relating to the lifting of this type of equipment should
be observed.

Use the lifting eye bolts provided.

Use the appropriate spreader bars/lifting slings with the holes/lugs provided.

Attach lifting chains to the 4 lifting eye bolts, each chain and eye bolt must be
capable of lifting the whole chiller.

Lift the unit slowly and evenly.

If the unit is dropped, it should immediately be checked for damage and reported
to Airedale Service.

CAUTION

Only use lifting points provided.

The unit should be lifted from the base and where possible, with all packing and
protection in position. If any other type of slinging is used, due care should be taken to
ensure that the slings do not crush the casework or coil.

N

P

R

P1

P2

P3

P4

C of G2

C of

G

1

T

S

LIFTING DIMENSIONS

N

P

R

S

T

URAC 75 - 125

mm

370

1060

370

2100

850

URAC 150 - 250

mm

370

1260

370

2100

850

URAC 240 - 450

mm

885

1900

415

2100

990