Fan performance - return air, Storemaster ™ comfort, Performance data – Airedale StoreMaster 50kW - 77kW User Manual

Page 34

Advertising
background image

STOREMASTER

Comfort

34

Comfort Range

Technical Manual : 6678403 V1.3.0_ 02_2013

Performance Data

FAN PERFORMANCE - RETURN AIR

Input voltage signal

The input voltage signal to the fan speed controller from the unit microprocessor (Vdc) sets
the fan speed for design performance.

The voltage can be determined from the graphs at design air volume using the Total
Static Pressure:

ESP

IP

TP

Where:
TP

= Total static pressure

IP

= Internal unit static pressure at 0Pa ESP

ESP = External static pressure at design conditions

Internal static pressure

The IP at 0Pa ESP can be determined at design air volume using the system lines
provided on the graphs:

1 = 0 Pa ESP - 100% Free Cooling
2 = 0 Pa ESP - 0% Free Cooling

Select the correct internal system line for the chosen design, (recommended design set up
at 100% free cooling operation).

Example

STM50

Air volume, design

= 2.7 m³/s

External static pressure, design

= 32 Pa

Internal static pressure, from graph = 48 Pa at 100% free cooling
Total static pressure, calculate

= 32 + 48 = 80 Pa

Input signal voltage, from graph

= 5.1 V

S

tat

ic

P

res

s

ure (

P

a)

0

20

40

60

80

100

120

140

1.50

1.75

2.00

2.25

2.50

2.75

3.00

3.25

80

1

2

3V

4V

5V

6V

8V

40

D

e

s

ig

n

E

S

P

2.75

Air Volume m³/s

Design Return Air
Volume

In line with current building guidelines on air quality, the return air volume has been
designed to provide a maximum of 90% of the supply air volume, thus ensuring a
constant 10% fresh air demand.