Standard features - general, Storemaster ™ comfort, General description – Airedale StoreMaster 50kW - 77kW User Manual

Page 6

Advertising
background image

STOREMASTER

Comfort

6

Comfort Range

Technical Manual : 6678403 V1.3.0_ 02_2013

General Description

STANDARD FEATURES - GENERAL

Construction

The base is fabricated from galvanised steel to ensure a tough, durable,
weatherproof construction.

Unit support can be provided by concrete/steel pillars to each corner of the rigid
steel base.

The superstructure is manufactured from galvanised sheet steel coated with epoxy baked
powder paint to provide a durable and weatherproof finish.

Standard unit colour is Light Grey (RAL 7035).

Compressors are mounted on a rigid galvanised heavy-duty sub frame. Fully
weatherproofed electrical panels are situated at one side of the unit. Access to all major
components sections of the unit are via either hinged or removable panels.

Construction includes duct flanges/mounts to accept self support ducting of up to 4m.

A set of removable 4 M24 collared lifting eye bolts to BS4278 are supplied.

Refer to

Dimensional Data

, on page 41 for unit layout.

Weather Louvres - Packaged

A weatherproof louvre is fitted to the fresh air intake and exhaust air as standard, to
protect internal components, complete with bird mesh.

Refer to

Weather Louvres - Split System

, on page 14 , for split system louvre arrangement.

Refrigeration

As standard the packaged unit is supplied with a full operating charge of R410A
refrigerant.

As standard the split unit is supplied with sufficient charge of R410A refrigerant to cover
5m of interconnecting pipe work. Refer to

Split Delivery

, on page 13 for split

case arrangement.

The cooling only unit has a single refrigeration circuit.

The Heat Pump unit has a two independent refrigeration circuits.

For further details, refer to

System Pipework Schematic

, on page 20.

Cooling Only Unit

EVAPORATOR SECTION INCLUDES:

Electronic expansion valve (EEV)

Liquid line sight glass

Discharge line ball valve

Large capacity filter drier

Low pressure switch with manual reset via microprocessor controller

High pressure switch with manual reset

Suction and liquid pressure transducers

CONDENSING SECTION INCLUDES:

Liquid line ball valve

5/16” Schrader for gauge connection