Installation Data
INTERCONNECTING WIRING
Heat Pump - Typical Example
Packaged Unit
&
Split System Evaporator
Section
STM..RHP-P
&
STM..RHP-E
L1
Mains incoming supply 400V / 3 PH / 50Hz
L2
L3
PE
L4
Separate Permanent Supply 230V / 1 PH +N / 50Hz (Option)
N1
PE
502
Unit Remote On/Off 24VAC
505
502
Fire Shutdown
507
565
Volt Free Common Alarm
Critical
564
Volt Free Alarm N/O
563
Volt Free Alarm N/C
562
Volt Free Common Alarm
Non-Critical
561
Volt Free Alarm N/O
560
Volt Free Alarm N/C
500
502
Return Air Velocity (Option)
858
801
852
Remote Outdoor Temp/Hum Sensors (Option)
853
860
Space Sensor 1 (Option)
861
862
Space Sensor 2 (Option)
853
RX-/Tx-
RX+/Tx+
Network Connections
GND
Split System Interconnecting
Wiring
STM..RHP-C
&
STM..RHP-E
3
Outdoor Drip Tray Heaters
N
216
Outgoing supply 400V/3PH/50Hz Connection to Condenser Fan 1
217
218
PE
222
Outgoing supply 400V/3PH/50Hz Connection to Condenser Fan 2
223
224
PE
527
502
Outdoor Fan status
528
840
Circuit 1 Outdoor Coil Temperature
841
842
Circuit 2 Outdoor Coil Temperature
843