Comfort

STOREMASTER

Comfort Range

49

Technical Manual : 6678403 V1.3.0_ 02_2013

Installation Data

INTERCONNECTING WIRING

Heat Pump - Typical Example

Packaged Unit
&
Split System Evaporator
Section

STM..RHP-P

&

STM..RHP-E

L1

Mains incoming supply 400V / 3 PH / 50Hz

L2

L3

PE

L4

Separate Permanent Supply 230V / 1 PH +N / 50Hz (Option)

N1

PE

502

Unit Remote On/Off 24VAC

505

502

Fire Shutdown

507

565

Volt Free Common Alarm

Critical

564

Volt Free Alarm N/O

563

Volt Free Alarm N/C

562

Volt Free Common Alarm

Non-Critical

561

Volt Free Alarm N/O

560

Volt Free Alarm N/C

500

502

Return Air Velocity (Option)

858

801

852

Remote Outdoor Temp/Hum Sensors (Option)

853

860

Space Sensor 1 (Option)

861

862

Space Sensor 2 (Option)

853

RX-/Tx-



RX+/Tx+



Network Connections

GND



Split System Interconnecting
Wiring

STM..RHP-C

&

STM..RHP-E

3

Outdoor Drip Tray Heaters

N

216

Outgoing supply 400V/3PH/50Hz Connection to Condenser Fan 1

217

218

PE

222

Outgoing supply 400V/3PH/50Hz Connection to Condenser Fan 2

223

224

PE

527

502

Outdoor Fan status

528

840

Circuit 1 Outdoor Coil Temperature

841

842

Circuit 2 Outdoor Coil Temperature

843