Unit lifting, Weights (kg), Comfort storemaster – Airedale StoreMaster 50kW - 77kW User Manual

Page 45: Installation data

Advertising
background image

Comfort

STOREMASTER

Comfort Range

45

Technical Manual : 6678403 V1.3.0_ 02_2013

Installation Data

UNIT LIFTING

Employ lifting specialists.

Local codes and regulations relating to the lifting of this type of equipment should
be observed

Use the appropriate spreader bars/lifting slings with the holes/lugs provided

Attach individual lifting chains to each of the lifting eye bolts/lifting lugs provided;
each individual chain must be capable of lifting the whole unit

IMPORTANT

Do not use 1 chain between 2 lifting points to avoid load shift.

Only use lifting points provided.

Chains/slings MUST NOT interfere with the casing or fan assembly to avoid damage

Lift the unit slowly and evenly

IMPORTANT

If the unit is dropped, it should immediately be checked for damage and reported
to Airedale.

LIFTING DIMENSIONS

Packaged Unit (mm)





A = 3.5m Minimum

A

2100

Split System (mm)

Evaporator Section

Condenser Section





A = 3m Minimum

A

2100

A

2100

WEIGHTS (KG)

Packaged (No Options)

Evaporator Section

Condenser Section

STM50R

kg

1987

1605

382

STM77R

kg

2003

1617

386

STM50RHP

kg

2146

1740

406

STM77RHP

kg

2150

1742

408