Installation Data

SPLIT SYSTEM

Connecting Refrigerant Pipework Sizing Guide

Evaporator
Section

Condenser
Section

Equivalent Pipe Lengths with R410A

In Cooling or Heat Pump Mode

Equivalent Length

Liquid

Discharge

SM50R-E

SM50R-C

0-15m

3/4”

1 1/8”

15-40m

7/8”

1 3/8”

SM77R-E

SM77R-C

0-15m

7/8”

1 3/8”

15-40m

7/8”

1 3/8”

SM50RHP-E

SM50RHP-C

0-15m

5/8”

1 1/8”

15-40m

5/8”

1 1

/8”

SM77RHP-E

SM77RHP-C

0-15m

5/8”

1 1/8”

15-40m

3/4”

1 1/8”

IMPORTANT

Liquid Line - The figures quoted are the recommended size for both cooling and heating
mode liquid lines.

Discharge Line - The discharge sizing recommendations quoted are also valid in heating
mode when this line becomes the suction line.

Unit Refrigerant Charge

The system refrigerant charge is supplied in the Condensing section and is sufficient for
approximately 5m of interconnecting pipework.

R410A

Pre charge

Amount of system charge required by

Evaporator section

SM50R-C

kg

23.8 SM50R-E

kg

14.0

SM77R-C

kg

27.7 SM77R-E

kg

16.8

SM50RHP-C

kg

2 x 17.7 SM50RHP-E

kg

2 x 11.1

SM77RHP-C

kg

2 x 19.0 SM77RHP-E

kg

2 x 12.4

IMPORTANT

Charges quoted per circuit ie: Cooling units have 1 circuit

Heat Pumps units have 2 circuits

Liquid Line Refrigerant
Charge (kg/m)

The condensing section is supplied with the system refrigerant and sufficient for approximately 5m of
interconnecting pipework. For every metre thereafter, the following table indicates the approximate
additional refrigerant required, using R410A and assuming a liquid line temperature of 40°C.

Liquid Line (m)

kg/m

3/8”

0.05

1/2”

0.09

5/8”

0.15

3/4”

0.21

7/8”

0.30

1 1/8”

0.53

Example: STM50R

Liquid Line length 15m (- 5m)

= 10m

Liquid Line diameter

= 3/4”

Addition Refrigerant per metre = 0.21kg

ie: 10 x 0.21 = 2.1kg of additional refrigerant / per circuit.

IMPORTANT

The pipe sizes/refrigerant charges quoted are for guidance only. It is the responsibility of
the installing contractor/site engineer to check the pipe sizes/refrigerant charge are correct
for each system installation and application.

Split systems may require additional oil which should be added to the low side of
each compressor.

Design should be in accordance with accepted refrigeration practice to ensure good oil
return to the compressor(s) under all normal operating conditions.