Installation Data
POSITIONING
The installation position should be selected with the following points in mind:
Position on a stable and even base, levelled to ensure that the compressor
operates correctly
The minimum unit support can be provided by concrete/steel blocks of 300 x 300
wide by 150mm deep to each corner of the rigid steel base
Levelling should be to +/- 5mm
Observe airflow and maintenance clearances
Pipework and electrical connections are readily accessible
Where multiple units are installed, due care should be taken to avoid the discharge
air from each unit adversely affecting other units in the vicinity
Within a side enclosed installation, the Condenser fan MUST be higher than the
enclosing structure
Ensure there are no obstructions directly above the fans
Allow free space above the fans to prevent air recirculation
Take particular care to ensure sufficient air circulation is available for units
fitted with optional Indirect Gas Fired Heating
IMPORTANT
Indirect Gas Fired Heating Option - As standard, configured suitable for outdoor
application only, UNLESS otherwise stated at time of order.
The unit MUST be checked prior to installation to ensure that it is correctly
configured for the application. If necessary, instructions for conversion are
supplied separately with the unit.
CAUTION
Prior to connecting services, ensure that the equipment is installed and
completely level.
Packaged (mm)
(1)
Service area require for
removal of coil
800
4500
1000
2480
720
3100
80
0
40
0
12
00
19
00
(1)
Split System (mm)
(1)
Service area require for
removal of coil
Evaporator Section
Condenser Section
800
3500
300
2480
720
1400
800
400
1200
1900
(1)
300
1000
1000
800
800
19
0
0