Comfort Range

Technical Manual : 6678403 V1.3.0_ 02_2013

Installation Data

POSITIONING

The installation position should be selected with the following points in mind:

Position on a stable and even base, levelled to ensure that the compressor
operates correctly

The minimum unit support can be provided by concrete/steel blocks of 300 x 300
wide by 150mm deep to each corner of the rigid steel base

Levelling should be to +/- 5mm

Observe airflow and maintenance clearances

Pipework and electrical connections are readily accessible

Where multiple units are installed, due care should be taken to avoid the discharge
air from each unit adversely affecting other units in the vicinity

Within a side enclosed installation, the Condenser fan MUST be higher than the
enclosing structure

Ensure there are no obstructions directly above the fans

Allow free space above the fans to prevent air recirculation

Take particular care to ensure sufficient air circulation is available for units
fitted with optional Indirect Gas Fired Heating

IMPORTANT

Indirect Gas Fired Heating Option - As standard, configured suitable for outdoor
application only, UNLESS otherwise stated at time of order.

The unit MUST be checked prior to installation to ensure that it is correctly
configured for the application. If necessary, instructions for conversion are
supplied separately with the unit.

CAUTION

Prior to connecting services, ensure that the equipment is installed and
completely level.

Packaged (mm)

(1)

Service area require for
removal of coil

800

4500

1000

2480

720

3100

80
0

40
0

12
00

19
00

(1)

Split System (mm)

(1)

Service area require for
removal of coil

Evaporator Section

Condenser Section

800

3500

300

2480

720

1400

800

400

1200

1900

(1)

300

1000

1000

800

800

19
0

0