General Specification

ELECTRICAL DATA - HEAT PUMP

(1)

STM50RHP

STM77RHP

Electrical Supply Data

Mains supply

(2)

V

400V / 3 PH / 50HZ

Permanent supply

Vac

230V / 1 PH + N / 50Hz

Control circuit

V

24vac/230vac

Recommended mains fuse

A

50

80

Recommended permanent mains fuse (3)

A

16

16

Max mains incoming cable size

mm

2

35mm² (direct to isolator)

35mm² (direct to isolator)

Max permanent incoming cable size

mm

2

4mm² terminals

Nominal run amps

(4)

A

43.0

59.9

Maximum start amps

(5)

A

184

197.3

Evaporator Fan - Per Fan

Quantity

2

2

Motor size

kW

1.9

3.6

Full load amps

A

3.1

5.9

Locked rotor amps

A

N/A

N/A

Type of start

Electronically Commutated

Condensing Unit Fans - Per Fan

(6)

Quantity

2

2

Motor size

kW

0.88

0.88

Full load amps

A

1.65

1.65

Locked rotor amps

A

6.1

6.1

Type of start

Direct on line

Compressors - Per Compressor

Quantity

2

2

Motor size

kW

8.4

12.15

Nominal run amps

(4)

A

15

20.66

Start amps

A

156

158

Oil heater rating

W

65

65

Type of start

Direct on line

OPTIONAL EXTRAS

Return air fan

(7)

Quantity

1

1

Plug fan motor

kW

1.4

2.1

Nominal run amps

A

2.7

5.8

Start amps

A

9.8

24

Electronic compressor soft start

Nominal run amps

(4)

A

15

20.66

Maximum start amps

(5)

A

93.6

94.8

Recommended mains fuse

A

50

80

Electric heating

(8)

Stage of reheat

2

3

Number of elements

6

9

Rating of electric heating

kW

24

36

Current per phase

A

34.7

52

(1)

Packaged Unit - P - Basic Unit (No Options)

(2)

When a common supply is used, a neutral is required.

(2)

Recommended permanent mains fuse is 32A when either a gas burner or power socket is fitted to the unit.

(3)

Based on 7.2°C evaporating and 54.4°C condensing.

(4)

Starting Amps refers to direct on line connections.

(5)

Sub fused when the unit is supplied split.

(6)

For units with options, unit fuse size needs to be calculated from information provided. Sizes given relate to basic units.

(7)

Electric heating to Heat Pumps is only supplementary.