Badger Meter E-Series Ultrasonic Meters User Manual

Page 10

Advertising
background image

Status

Indicator

Icon

Alarm Description

High Resolution

with ORION

Cellular, Fixed

Network (SE) or

Migratable (ME)

Encoder Protocol

with ORION

Cellular, Fixed

Network (SE) or

Migratable (ME)

RTR with

ORION Fixed

Network (SE) or

Migratable (ME)

Meter

functioning

correctly

Meter operating correctly

Normal operation

Indicator not sent

to endpoint

Normal operation

Indicator not sent

to endpoint

Normal operation

Indicator not sent to

endpoint

Meter alarm

Several potential conditions may

exist, including:
• Empty pipe: “err” displays on

LCD Alarm clears when pipe

is filled

• Low Temperature limits

exceeded: meter continues to

operate but outside specified

accuracy range Alarm clears

after 35 days unless alarm

condition continues

• Maximum flow rate is exceeded

No consumption is displayed

until back within specified

flow range Both the meter

functioning correctly and the

meter alarm are active

• Other meter or sensor issue:

meter continues to operate if

possible Alarm clears after

35 days unless alarm

condition continues

Consumption

data is sent to the

endpoint Meter

Alarm is also sent

Meter Alarm is sent

to the endpoint
NOTEE: No

consumption data

is sent to endpoint

when the alarm

is active

Consumption

data is sent to the

endpoint, except

when Exceeding

Max Flow Alarm

is set

Reverse flow

The meter detects reverse flow

and triggers the reverse flow alarm

icon on the E-Series display The

alarm remains active for 35 days

The alarm automatically clears

after 35 days if the condition has

not recurred

Meter detects

reverse flow

and sends alarm

message to

the endpoint

Meter does not

send the alarm The

endpoint detects

and reports the

reverse flow and

will report the

read exactly how it

is received

No alarm condition

reported by the

endpoint will only

record positive,

forward flow

Suspected

leak

Meter detects 24 hours without

one 15-minute interval of no flow

The alarm clears automatically

when a 15-minute no-flow

interval occurs

Meter detects

suspected leak

and sends alarm

message to

the endpoint

Meter does not send the alarm

The endpoint detects continuous

consumption over 24-hour period and

reports suspected leak

30 day no

usage

No measured flow in past 30 days

The alarm automatically clears

once flow occurs

Meter detects 30

day no usage and

sends alarm to

the endpoint

Meter does not send the alarm

The endpoint detects no change in

consumption over 30-day period and

reports 30 day no usage

End of life

battery

indicator

Indicated battery life based on pre-

calculated consumption Alarm

is activated after 19 years and 6

months and does not clear

Meter sends alarm

to the endpoint

Meter does not send the alarm

E-Series® Ultrasonic Meters for Fire Service Applications

Page 10

August 2014