Meter storage mode, Meter pre-installation, Meter storage mode 4 – Badger Meter E-Series Ultrasonic Meters User Manual

Page 4: Meter pre-installation 4

Advertising
background image

METER STORAGE MODE

All E-Series Ultrasonic meters are delivered in a storage mode so that a meter alarm is not triggered During storage mode,

the empty pipe shows up on the LCD display as an error message, but it will not trigger a meter alarm The meter needs to

sense a full pipe for 24 hours for the meter to go from storage mode to normal operation If installed when the meter is still in

storage mode, the meter will function as expected with the addition of also displaying “err” on the flow rate screen The meter

will display consumption and, if connected to AMR/AMI, will send a reading to the endpoint When the meter is in normal

operation, the meter alarm displays immediately upon detecting the empty pipe condition The alarm clears immediately

after the condition is corrected and the pipe is full Systems that support the additional alarm conditions will be notified that

an empty pipe condition has occurred

METER PRE-INSTALLATION

Take into account the following considerations before you begin an installation:

Inspect the piping around the meter setting for suitable conditions The service line, valves, connections and meter

must be watertight Repair the piping system if pipes are corroded or damaged

Set the meter in a horizontal or vertical position with flow in the up direction Registration should be upright and

protected from damage, freezing and tampering

Position the meter so it is accessible for installation, removal and reading

Verify that a suitable, electrical grounding wire is properly attached to the upstream and downstream pipe

connections of the meter The grounding wire provides an alternative path for any electrical current that may exist

across the opening in the line

Close the curb (shutoff) valve to relieve water pressure in the line before starting the cutting operation Provide a

high-quality upstream shutoff valve with a low pressure drop

When cutting into a new section of service pipe, flush the pipe to clear chips, pipe dope or other plumbing residue

For the 3/4" and 1" meters, the line opening in which the meter is to be set should match the laying length of the

meter, allowing slight additional space for coupling gaskets The inlet and outlet sides of the meter setting should be

axially aligned to the pipe

For the 1-1/2" and 2" meters, the line opening in which the meter is to be set should match the laying length of the

meter For optimal performance and accuracy, it is also recommended that a minimum of five diameters of straight

pipe be installed upstream of the meter

The installed meter must not be an obstacle or a hazard to the customer or interfere with public safety

DO NOT ATTEMPT TO USE ANY METER AS A LEVER OR CROWBAR TO STRAIGHTEN A MISALIGNED METER SETTING.

THIS COULD DAMAGE THE METER.

DO NOT ATTEMPT TO SET A METER INTO AN OPENING THAT IS TOO LONG BY FORCING THE PIPING INTO PLACE

WITH THE METER'S COUPLING NUTS. THIS WILL CAUSE SERIOUS DAMAGE TO THE THREADED ENDS OF THE METER

AND HOUSING.

TO AVOID POTENTIAL PROBLEMS, CORRECT ANY IRREGULARITIES IN PIPE SPACING AND MISALIGNMENT BEFORE

PLACING THE METER INTO ITS SETTING.

E-Series® Ultrasonic Meters for Fire Service Applications

Page 4

August 2014