Output option card, Usb port, Installation & operation manual – Badger Meter 3100 Series Flow Monitor User Manual

Page 13

Advertising
background image

Page 13

2-12

Installation & Operation Manual

OUTPUT OPTION CARD

If the Series 3000 Flow Monitor was ordered with the Output Option card, it will have several additional outputs.

1. Analog Output ( 0-20mA; or 4-20mA ) which can be converted externally to 0-5VDC, 1-5VDC with a 250 Ohm resistor; or

0-10VDC or 2-10VDC with a500 Ohm resistor. A 15VDC power supply is provided to permit current sinking or sourcing. The

Series 3000 has special software that permits the Analog output.

2. USB for direct access to a computer using a standard mini-USB cable.

3. RS-485 for fully addressable Modbus or BACnet communication.

1 RS485 B

2 RS485 A

3 RS485 GND

4 LOOP +

5 LOOP -

6 GND

Figure 10: Current Sourcing Analog Output

1 RS485 B

2 RS485 A

3 RS485 GND

4 LOOP +

5 LOOP -

6 GND

Figure 11: Current Sinking Analog Output

1 RS485 B

2 RS485 A

3 RS485 GND

4 LOOP +

5 LOOP -

6 GND

Figure 12: Analog Output Wiring

USB Port

NOTE: To communicate using the USB port requires Windows HyperTerminal or other similar communications

software. This port is part of the Analog Output Option card. See the USB Communications section of

PROGRAMMING on page 19 for instructions on how to use this port.