Badger Meter 3100 Series Flow Monitor User Manual

Page 22

Advertising
background image

Page 22

2-12

Series 3000 Flow Monitor

RELAY OUTPUT CONFIGURATION

relay [1-5] func = [0-9] – relay function; relay 5 is the

pulse output

0: Totalizer

1: Alarm

2: Manual Control

relay [1-5] input = [0-8] – relay input; depends on source

for totalizer:

0: Flow 1 Total

for alarms:

0: Flow 1 Rate

relay [1-5] units = [0-19] – units on setpoints/rates;

depends on

src/input

flow units: same as 'flow [1-2] rate units' above

volume units: same as 'flow [1-2] total units'

relay [1-5] manual = [on/off] – manually set relay on or

off, if in manual mode

relay [1-5] rate = [x] – totalizer rate

relay [1-5] ctime = [0-10000] – pulse width in millisec-

onds

relay [1-4] latch = [on/off] – turn on/off relay latching

relay [1-4] setpoint = [x]

relay [1-4] releasepoint = [x]

ANALOG OUTPUT CONFIGURATION

analogout [1-2] func = [0-3]

0: Flow rate

3: PID control

analogout [1-2] src = [0-4]

for flow rate:

0: Flow 1 rate

for PID control:

0: Flow 1 rate

analogout [1-2] range = [0-1]

0: 0-20mA

1: 4-20mA

analogout [1-2] low = [x] – value corresponding to

0 (or 4) mA

analogout [1-2] high = [x] – value corresponding to

20mA

analogout [1-2] setpoint = [x] – PID setpoint

analogout [1-2] P = [x] – PID constants

analogout [1-2] I = [x] – PID constants

analogout [1-2] D = [x] – PID constants

RS485 COMM PORT CONFIGURATION

comm baudrate = [0-7]

0: Auto

1: 300

2: 1200

3: 2400

4: 9600

5: 19200

6: 38400

7: 76800

comm mstpaddr = [0-127] – BACnet/MSTP address

comm maxmaster = [0-127] – BACnet/MSTP max master address

comm devinst = [x] – BACnet device instance ID

comm mbslaveaddr = [0-255] – Modbus slave address

TROUBLESHOOTING

Trouble Codes:

1 Relay 1 totalizer rate exceeded

2 Relay 2 rate exceeded

3 Relay 3 rate exceeded

4 Relay 4 rate exceeded

5 Pulse out rate exceeded

20 Error reading EEPROM on faceplate

21 Error writing EEPROM

22 Analog Input card missing

24 Temperature Input card missing

25 Invalid flow units configured

26 Invalid volume units configured

27 Bad input frequency

29 Internal error calculating flow rate

31 Error reading from analog input AD converter channel 1

32 Error reading from analog input AD converter channel 2

36 Error writing to analog input AD converter channel 1

37 Error writing to analog input AD converter channel 2

50 Error reading I2C address 0 (relays, buttons, and LEDs)

51 Error writing to I2C address 0

52 Error reading I2C address 1 (analog input card control lines)

53 Error writing I2C address 1

54 Error reading I2C address 2 (temperature input card control lines)

55 Error writing I2C address 2

71 Watchdog timer reset occurred

82 Fatal error initializing EEPROM