Electrical Installation

Power Supply Wiring

The Series 3000 Flow Monitor requires 12-24 VDC/VAC to operate. Check the Specifications on page 23 for DC current draw

and AC Volt-Amp requirements.

A fused circuit is always recommended. Connect the positive of the power supply to the Series 3000 terminal marked

(ACL/DC+), and connect the negative of the power supply to the Series 3000 terminal marked (ACC/DC-).

If a Badger Meter Data Industrial plug-in power supply (Model A1026, A-503) is being used, connect the black-white wire to

the terminal marked (ACL/DC+) and the black wire to the terminal marked (ACC/DC-).

Earth

3

LV AC/DC(-) 2

LV AC/DC(+) 1

POWER

Figure 3: Power Supply Wiring

Flow Sensor Wiring

The Series 3000 flow sensor inputs are extremely versatile, designed to accept either two-wire or three-wire pulse inputs

(Data Industrial 200 Series, 4000 Series) or Analog inputs. Although different rear panel terminals are used, all parameters are

set with the LCD/keypad interface. There are no internal or external jumpers, switches or potentiometers to move or adjust.

The following pulse input types are accommodated.

Pulse-DI: Used for all Badger Meter Data Industrial Flow Sensors. Provides an internal pull-up resistor and uses “K”

and “Offset” values for calibration.

Pulse–K Factor: Accepts non zero-crossing inputs but provides no internal pull-up, classical “K” ( pulses/gallon)

values for calibration.

Pull-up-K Factor: Provides an internal pull-up resistor and uses classical “K” ( pulses/gallon) values for calibration.

NOTE: All the above pulse input types wire the same as shown in Figure 4. See the Programming Flow Chart on

page 16 for required input configuration.