Badger Meter Vortex Meters User Manual

Page 11

Advertising
background image

11

09-VRX-UM-00408 07/12

Pulse Output

The pulse output is a secondary output and is not intended for long transmission. The load on the line must be 50 kilohm
minimum and 1,000 picofarads (pf ) maximum.

The maximum length of shielded cable that can be attached to this output is 100 feet.

Cable Installation

To install the cable in the fl ow meter, route the cable through the cable gland located on the electronics enclosure.

The wiring of the other end of the cable will vary depending on the specifi c installation requirements. Figures 6, 7, and 8 show
the wiring diagram for variations of fl ow meter installation.

The fl ow meter’s 4 position terminal strip provides all the connections needed to operate the fl ow meter.

+ 4-20 mA Terminals

The + 4-20 mA terminals are used for the fl ow meter’s power supply. This power supply should be 10 to 30 Volt DC and be capable
of supplying 25 Milliamp to the fl ow meter. Because this meter has a built-in display no additional wiring is necessary for basic
operation (See Figure 6).

4-20

P

ulse

XMIT

RECV

+

-

+

-

2 CONDUCTOR

SHIELDED CABLE

CURRENT OUTPUT 2 WIRE HOOKUP

STAND ALONE POWER SUPPLY

10-30 VDC

POWER SUPPLY

FIGURE 6 - DEDICATED POWER SUPPLY HOOKUP