Badger Meter Vortex Meters User Manual

Page 7

Advertising
background image

7

09-VRX-UM-00408 07/12

Upstream Obstruction

Minimum Required Straight-run Pipe

Diameters Upstream from Meter

90° Elbow

10

Two 90° Elbows, Same Plane

15

Two 90° Elbows, Diff erent Planes

20

Flow Straightener

(recommended when ever an axial swirl exists in the fl ow stream)

10

Fully Open Shut-off Valve

5

Downstream Obstruction

Minimum Required Straight-run Pipe

Diameters Downstream from Meter

Control Valve

5

TABLE 1 - MINIMUM PIPING REQUIREMENTS

NOMINAL SIZE

INCH (mm)

GALLONS PER MINUTE (gpm)

LITERS PER MINUTE (lpm)

Minimum Flow

Maximum Flow

Minimum Flow

Maximum Flow

4.0 (100)

79

635

300

2,403

6.0 (152)

180

1441

682

5,454

8.0 (203)

312

2,495

1,181

9,444

10.0 (254)

492

3,933

1,861

14,886

12.0 (305)

698

5,582

2,641

21,130

14.0 (356)

843

6,746

3,192

25,537

16.0 (406)

1,102

8,813

4,170

33,360

18.0 (457)

1,394

11,155

5,278

42,226

20.0 (508)

1,733

13,864

6,560

52,481

Based on water at 1 centistoke at 73° F, schedule 40 pipe 1 to 20 fps (0.3 to 6 mps). For reference only, consult sizing
program for temperature and pressure conditions other than those listed here.

TABLE 2 - FLOW RANGES