Electrical Installation: Relay Board (Optional)

24

Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510D

Relay Board functions

The Relay Board informs the user of the operation mode, status, and alarm conditionsand has 8 ports
on the input side and 16 output terminals.

Note

Use Normally Closed (NC) contacts for Fail safe Mode and Normally Open (NO) for
Active on.

Relay
ID

Name

Events that will trigger the alarm

Mode

Comment

K1

Common Alarm

• Any of the functions below, except relays

K8, K9, K10, K11;

• Inverter section fault;
• Main PSU fault;
• System locked in operation mode;
• Internal memory fault;
• Internal communication fault.

Fail safe

Warning

K2

Battery voltage out of
tolerance

• DC voltage is too high (shut down);
• DC voltage is under warning level;
• DC voltage is low (shut down).

Fail safe

Warning

K3

Mains out of tolerance

• Mains voltage RMS value is out of

tolerance;

• Mains waveform not accepted (fast

detector);

• Mains frequency is out of tolerance.

Fail safe

Warning

K4

Bypass out of tolerance

• Bypass voltage RMS value is out of

tolerance;

• Bypass waveform not accepted (fast

detector);

• Bypass frequency is out of tolerance.

Fail safe

Warning

K5

Battery condition fault

• Battery monitor has detected a weak

battery;

• Battery monitor has detected a defective

battery.

Fail safe

Fault

K6

Battery disconnected

• Battery breaker tripped/open.

Fail safe

Fault

K7

System overload

• Output load exceeded 100%;
• Delta Inverter current limiter is active;
• Main Inverter current limiter is active.

Fail safe

Fault

K8

Output out of tolerance

• Output voltage RMS value is out of

tolerance;

• Output waveform not accepted (fast

detector);

• Output frequency is out of tolerance.

Fail safe

Fault

K9

Normal operation

• UPS is running in normal operation.

Active on

Opr. mode

K10

Battery operation

• UPS is running in battery operation.

Active on

Opr. mode