Specifications: Electrical Specifications

30

Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510D

Notes

1. Nominal (Nom): Input current based on rated load, nominal input voltage and fully charged

batteries.

2. Current limitation is maximum allowed via electronic current limiting and is based on full

battery recharge + nominal load and -10% input voltage.

3. Nominal battery voltage assumed to be 2.0 volts/cell (lead technology).

4. Nominal Battery Discharge current based on rated load, and nominal Battery voltage.

5. Maximum Battery Discharge current based on rated load at end of Discharge.

6. Heat dissipation calculated at rated load capacity.

7. This current is at 125% of rated load and is electronically current-limited to a maximum of 10

minutes. This value is only provided so the engineer can ensure that the selected AC output
circuit overcurrent device’s time-current characteristic will support this condition.

8. At 380 V, nominal output is reduced from 200 kW to 180 kW in each section.

Torque specifications

Torque specifications

Bolt Size M8

13.5 Nm

Bolt Size M10

30 Nm

Bolt Size M12

50 Nm

Bolt Size M14

75 Nm