Required breaker settings (400 v systems), Input and upstream breakers — minimum settings, Output and downstream breakers -— minimum settings – American Power Conversion SYMF800KH User Manual

Page 37

Advertising
background image

Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510D

31

Required Breaker Settings (400 V Systems)

The Symmetra® MW is a fault-tolerant system capable of handling and surviving overloads and
internal/external faults. The overload performances and fault clearings are possible when the system
meets specified minimum requirements for breaker settings. The settings are specified in the tables
below, but some of them can also be found in the Electrical Specification section. The settings are all
minimum settings and may not result in a drop-out.

Input and upstream breakers — minimum settings

Output and downstream breakers -— minimum settings

Note

Contact APC Application Team for Required Breaker Settings in 380 V and 415 V
systems.

See also

See separate guide on parallel operation for information on required breaker settings in
parallel systems.

Q1, Q5, and any upstream breaker

Duration [S]

Current [A]

Total load [%]

Event/Operation

< 0.005

22 kA

--

Internal fault clearing

1466*

127

Overload on-line

1195

100

On-line

1315

110

On-line+ Max. Battery

charge

* Only applicable to Q1

Q2, Q4, Q6, and any downstream breaker

Duration [S]

Current [A]

Total load [%]

Event/Operation

< 0.005

22 kA

--

Internal fault clearing.

60

2406*

200

Overload on-line

600

1504*

125

Overload on-line

1155

100

On-line

* Only applciable to Q2 and Q4