Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510D

Electrical Specifications

AC Input

WARNING!
Supply the UPS from a dedicated, 3 × 400/230 V, L1, L2, L3, N, PE source or a
high-impedance grounded system.

CAUTION!
Ensure clockwise phase rotation (L1, L2, L3) of input voltages.

CAUTION!
AC and DC disconnect switches and over-current protection must be included in the
installation.

Note

All wiring must comply with all applicable national and/or local electrical codes.

Note

Max. prospective RMS short-circuit current on input terminals: 200 kA
Max. prospective RMS short-circuit current on DC terminals: 50 kA

AC Input

Input rating

800 kW/kVA

Power Factor

1

Input Voltage

380 V

Input Frequency

50 Hz

Nominal input current (note 1)

1132 A

Input Current Limitation (note 2)

1422 A

Input Voltage

400 V

Input Frequency

50 Hz

Nominal input current (note 1)

1203 A

Input Current Limitation (note 2)

1466 A

Input Voltage

415 V

Input Frequency

50 Hz

Nominal input current (note 1)

1159 A

Input Current Limitation (note 2)

1447 A