MAXIM Installation Instructions

Page 28

© Mass Electronics Pty Ltd 2011

Edition 2.0 dated 20/11/2013

A single transformer may be used to supply voltage to more than one controller, but you must ensure

that the planned load is well within the rating of the transformer. The transformer output terminal

designated as AC Neutral must be solidly earthed to the main earth link of the enclosure panel. The

power input terminals are Terminals 1 and 2 and are detailed in Table 3-2 below.

3-3.1.1 Power Input

The MAXIM I, II, III, and 1010 controllers may by powered by either an AC or a DC power source. The

operating voltage must meet the requirements of Safety Extra Low Voltage (SELV) to EN60730. The

transformer used must be a safety transformer in compliance with EN60742 and be designed for

100% duty. It must also be sized and fused in compliance with local safety regulations. Power input

specifications for these controllers are detailed in Table 3-1 below.

Controller

AC Power Source

DC Power Source

MAXIM I and II

24VAC ±10%, 50/60 Hz,
Nominal Transformer

rating:

5VA

24VDC ±10%
Nominal Transformer

rating:

5VA

MAXIM III

24VAC ±10%, 50/60 Hz,
Nominal Transformer

rating:

10VA

24VDC ±10%
Nominal Transformer

rating:

10VA

MAXIM 1010

24VAC ±10%, 50/60 Hz,
Nominal Transformer

rating:

16VA

24VDC ±10%
Nominal Transformer

rating:

16VA

Table 3-1: 

MAXIM I, II, III and 1010 Power Source Specifications

Terminal

AC Supply

DC Supply

1

24VAC

24VDC

2

0VAC (Neutral)

0VDC

Table 3-2: 

MAXIM I, II, III and 1010 Controller Power Input Terminals