MAXIM Installation Instructions

© Mass Electronics Pty Ltd 2011

Chapter 5 – Commissioning

The steps below provide further details to check and verify proper operation of the Digital Relay

Outputs on MAXIM Series controllers, as illustrated in Figure 5-3 on the previous page.

1. Verify that the MAXIM controller on which the Digital Relay Outputs will be checked is powered

OFF. You must also verify that power is turned OFF to all of the digital output circuits to be

checked.

2. Beginning at the first device connected to the NO contacts, turn the power ON to the output

device.

3. Visually check to verify that devices connected between the NO and Com terminals are OFF.

If this cannot be verified by a simple visual observation, connect a DMM across the device to

measure the voltage. With the DMM set to the appropriate voltage, verify the that the measured

voltage reads 0V.

4. Verify that the device is OFF by either visual inspection of the device itself, or verifying that the

measured reading on the DMM is 0V.

5. Temporarily connect a jumper wire between the NO and Com contacts of the Digital Relay

Output to be checked. Verify that the jumper wire is of adequate size to temporarily carry the

load.

6. Now turn the power ON to the output device.
7. Verify that the device is ON by either visual inspection of the device itself, or verifying that the

measured reading on the DMM is the expected operating voltage of the device.

8. Turn the power to the output device OFF.
9. Remove the jumper wire connected in Step 6.
10. Repeat Step 2 through Step 10 for the remaining output devices connected to the NO contacts.