Innotech Maxim User Manual

Page 30

Advertising
background image

MAXIM Installation Instructions

Page 30

© Mass Electronics Pty Ltd 2011

Edition 2.0 dated 20/11/2013

3-3.1.3 Analogue Outputs

The analogue outputs can be configured with MAXCon software to either heat valve mode or variable

mode to suit your requirements. Each analogue output has a signal terminal (+) and a shared Com

terminal (–). As illustrated in the connection details in Figure 3-1, the + terminal is the active signal,

and the Com terminal is the signal reference of 0V, which also can be referred to as ground.

It must be noted that on MAXIM Series I and II controllers only AO1 and AO2 can be configured to heat

valve mode. However on MAXIM Series III all 8 Analogue Outputs can be configured to heat valve

mode.

When an analogue output is configured to heat valve mode, the output is a Pulse Width Modulated

(PWM) signal of 0 or 10V DC with a maximum current rating of 5m A. When an analogue output is

configured to variable mode, the output is an analogue voltage signal varying from 0 to 10V DC with a

maximum current rating of 5m A.

When an analogue output is configured as a PWM signal in heat valve mode, up to three Solid State

Relays (SSR) connected in series may be used on each analogue output channel, as illustrated in

Figure 3-6 below. The SSRs must be capable of a trigger voltage of 3 to 32V DC and zero switching.

1

2

3+ve

4

1

2

3+ve

4

1

2

3+ve

4

+

-

ANALOGUE

OUTPUT

TERMINALS

TO

HEATERS

TO

HEATERS

TO

HEATERS

L1

L2

L3

If up to 6 SSRs are to be wired in series, you can use the Analogue Output as 0 to 10V DC modulating

in conjunction with the Innotech Heat Valve (IHV) module. Please refer to the following datasheets

for more information on IHVs:

• DS3.31 for IHV Heat Valves

• DS3.32 for IHV42 Heat Valves

Figure 3-6:  Analogue Output Driving Multiple Solid State Relays

Advertising