Appendix A – Using the CT01 Commissioning Tool

A-5.1 Calibration of sensors

The calibration of sensors is normally completed by the Innotech commissioning technicians.

However the CT01 can be used to calibrate the sensor if the need arises. Follow the steps below to

calibrate sensors:

1. Log onto a VAVMax controller as per the instructions in the previous section.
2. Select Commission and press the

Enter button.

3. Select Calibrate and press the

enter button.

4. Each port corresponds to an input on the VAVMax controller. Port 3 is a dedicated temperature

input.

5. To calibrate temperature input, take a note of the sensor reading with a reliable thermometer.
6. Scroll to Port 3 and press the

Enter button.

7. Using the navigation buttons enter the correct measured temperature and press the

Enter

button.

8. This will calibrate the sensor and provide an offset reading.
9. This same process can be used if Ports 1 or 2 are used for temperature inputs.
10. Press the

Exit button repeatedly to return to the main menu..

11. The commissioning process is now complete.

A-5.2 Configuring the K-Factor

The K factor value is required to be calibrated to allow the VAVMax controller to correctly read the

pressure and calculate the airflow. The VAVMax does not need to know the duct size because it

is contained within the K factor. The K factor can be set manually, or the VAVMax can calculate it

automatically by following the steps below:

1. Log onto a VAVMax controller as per the instructions in the previous section.
2. Select Commission and press the

Enter button.

3. Select Calibrate and press the

enter button.

4. Scroll down to

Port 4. The parameters Measured and K factor should be visible on the LCD. The

Measured

value is the airflow the VAVMax is currently reading.

5. Press the

Enter button to calibrate the Measured value. Using the navigation buttons enter

your total measured air volume in L/S for that particular VAVMax controller, and press the

Enter

button.

6. The VAVMax will now be calibrated and the K factor will be calculated.
7. Press the

Exit button repeatedly to return to the main menu.

The K-Factor may need to be rechecked and calibrated when the airflow is set to VMax.

NOTE

It is recommended to access and view the watch pages again to verify the controller is operating correctly. Verify

that the temperatures are correct, and the minimum and maximum air flows have been calibrated.