GC Series Central Chillers

Chapter 4: Operation

38 of 79

4-4 Access Levels

The controller is setup to allow access to three distinct password groups: operator, supervisor,
and service. Operator access allows the user to modify the Leaving Water Temp, Hi and Low
Temp Warning, Hi and Low Temp Fault setpoints. Supervisor access allows the supervisor to
modify the above plus additional setpoints, installing additional modules, setup
communications, and perform sensor calibration.

Selecting any of the menus in the Menu Screen will display the Password Screen if multiple
passwords were setup. See Section 3-10 for more information.

4-5 Controller Setpoints

Variable

Description

Access Level

Operator

Supervisor

Chiller/Process SP

Temperature of fluid leaving evaporator

x

x

Chil/Proc Hi Temp Wrn

Setpoint for alarm to warn when leaving fluid
temperature is too high

x

x

Chil/Proc Hi Temp Flt

Setpoint to shut down pump and compressor based on
leaving fluid temperature

x

x

Chil/Proc Hi Temp Dly

Delay time in minutes between fault and stopping the
compressor and pump

x

Hi Temp Flt Type

Select warning or critical for the desired type of high
temperature fault.

x

Proc Low Temp Wrn

Temperature to activate Low Temperature Warning
alarm

x

Proc Low Temp Flt

Temperature to activate Low Temperature Fault alarm

x

Cooling Enabled

Allows refrigeration circuit to be active

x

Heating Enabled

Allows process heating to be active

x

Fluid Freeze Pt

Minimum temperature of leaving fluid temperature
before fluid freezes

x

Chil On Diff

Temperature Difference between Leaving Fluid
Temperature and Setpoint to turn on the compressor

x

Chil Off Diff

Temperature Difference between Leaving Fluid
Temperature and Setpoint to turn off the compressor

x

Chil Lo T Wrn Diff

Chiller low temperature warning alarm based on a
differential from setpoint.

x

Chil Lo T Flt Diff

Chiller low temperature fault alarm based on a
differential from setpoint.

x

Comp,Lead Cmp On
Delay

Time in minutes before lead compressor can activate

x

Comp,Lead Cmp Off
Delay

Time in minutes before lead compressor can deactivate

x

Lag Cmp On Dly

Time in minutes after lead compressor activates before
lag compressor can activate

x

Lag Cmp Off Dly

Time in minutes after lead compressor deactivates
before lag compressor can deactivate

x

Cond Fan Start

Discharge pressure setting to activate condenser fans

x

Cond Fan Stop

Discharge pressure setting to deactivate condenser fans

x