Chapter 6: Troubleshooting

49 of 79

Controller Alarm

Possible Cause

Solution

High Level Warning (optional:
will only become active if level
sensor is enabled in Supervisor

Menu)

Fluid level in pump tank is above
warning setpoint

Remove fluid from pump tank to
achieve a minimum of 18 in (46 cm)
above the pump suction centerline

while the pump is operating

Compressor Differential Pressure
Fault

Condenser inlet temperature too
low

Contact ACS Group Aftermarket
Service for assistance

VFD fault

See VFD Fault above

Condenser water regulating valve
open

Verify analog output at Y1

High Suction Pressure Warning

Load may be too high for chiller

Contact your sales representative for

assistance.

Low Discharge Pressure Warning

Condenser inlet temperature too
low

Contact ACS Group Aftermarket
Service for assistance

VFD fault

See VFD Fault above

Condenser water regulating valve
open

Verify analog output at Y1

Low Fluid Temp Warning

Dirty evaporator

Clean evaporator inlet strainer
Back flush evaporator

Hot gas bypass valve malfunction

Verify wiring at EV Connection B1-4

Low Level Warning (optional: will

only become active if level sensor
is enabled in Supervisor Menu)

Fluid level in pump tank is below

warning setpoint

Add fluid to pump tank to a minimum

of 18 in (46 cm) above the pump
suction centerline while the pump is
operating

Compressor Differential Pressure

Warning

Condenser inlet temperature too

low

Contact ACS Group Aftermarket

Service for assistance

VFD fault

See VFD Fault above

Condenser water regulating valve

open

Verify analog output at Y1

Low Suction Pressure Warning

Refrigerant undercharge

Contact refrigeration technician about
adding refrigerant as needed

Refrigerant leak

Contact refrigeration technician about
repairing lead and adding refrigerant as
needed

Electronic expansion valve closed

Verify wiring EV Connection A1-4 on

EVD

Low fluid flow through evaporator

Verify evaporator inlet and outlet
butterfly valve position to achieve 10°F
(5.6°C) differential across evaporator
Clean evaporator inlet strainer
Verify evaporator pump operation

Leaving fluid temperature close to
Fluid Freezepoint Setpoint

Verify Fluid Freezepoint setpoint and
glycol/water mixture for proper
freezing temperature

Pump Down Override Time
Expired

Electronic valve malfunction

Verify wiring EV Connection A1-4 on
EVD

Optional Hot gas bypass valve
malfunction

Verify wiring EV Connection B1-4 on
EVD

Pump Flow Sensor Failure

Input to PLC is missing

Verify wiring at ID3 on PLC

M12 connector on cable separated
from sensor

Reconnect M12 connector to top of
sensor.

Faulty sensor cable

Replace cable

Faulty sensor

Replace sensor

Refrig Liquid Temp Sensor
Failure

Input to PLC is missing

Verify wiring at EVD

Faulty sensor

Replace sensor

Refrig Suction Temp Sensor
Failure

Input to PLC is missing

Verify wiring at EVD

Faulty sensor

Replace sensor

Tank Level Sensor Failure

Packard connector separated from
sensor

Reconnect wire connector to sensor

Input to PLC is missing

Verify wiring at PLC