Water-cooled central chillers – Sterlco GC Series Central Chiller User Manual

Page 60

Advertising
background image

GC Series Central Chillers

Chapter 7: Appendix

60 of 79

Water-Cooled Central Chillers

Nominal operating parameters for water-cooled models are 50ºF (10ºC) leaving water temperature at 2.4 gpm per ton
(9.1 lpm per 3.517 kW) with 85ºF (29ºC) tower water. For 50 Hz applications, multiply capacity by 0.83. Nominal 60
Hz capacity flow rate must be maintained.

20 TON (GCWC-70)

PERFORMANCE (NOMINAL DESIGN CONDITIONS)

COOLING CAPACITY

22.68

TONS

ALTITUDE

SEA LEVEL

COOLANT SUPPLY
TEMPERATURE

50

°F

COMPRESSOR POWER

16970

WATTS

CONDENSER INLET WATER
TEMP

85

°F

EER

16.04 BTU/WATT

COOLANT

WATER

CONDENSER WATER FLOW

68

GPM

COOLANT FLOW

54

GPM

SOUND POWER LEVEL

74

dBA

UNIT PRESSURE DROP

7

PSID

SOUND PRESS LEVEL @ 1
METER

dBA

OPERATING PARAMETERS

COOLANT SUPPLY
TEMPERATURE

20-80

°F

COOLANT FLOW

24-96

GPM

CONDENSER INLET WATER
TEMP

50-90

°F

MINIMUM LOAD

4.54

TONS

SPECIFICATIONS

COMPRESSOR

SCROLL

FRAME

GALVANIZED STEEL

EVAPORATOR

BRAZED PLATE

COOLANT CIRCUIT

NON-FERROUS

CONDENSER

SHELL &
TUBE

REFRIGERANT

22 LBS R-410A

EVAPORATOR FILTER

20 MESH

WEIGHT (OPERATING)

1660.95

LBS

POWER

460V/3PH/60HZ

WEIGHT (SHIPPING)

940.95

LBS

CONTROL CIRCUIT

24/120

VAC

ELECTRICAL ENCLOSURE

NEMA 4/12

COMPRESSOR RATED LOAD
AMPS

(2) @ 17.9 AMPS EACH

CONTROL

MICROPROCESSOR

Advertising