Water-cooled central chillers – Sterlco GC Series Central Chiller User Manual
Page 60

GC Series Central Chillers
Chapter 7: Appendix
60 of 79
Water-Cooled Central Chillers
Nominal operating parameters for water-cooled models are 50ºF (10ºC) leaving water temperature at 2.4 gpm per ton
(9.1 lpm per 3.517 kW) with 85ºF (29ºC) tower water. For 50 Hz applications, multiply capacity by 0.83. Nominal 60
Hz capacity flow rate must be maintained.
20 TON (GCWC-70)
PERFORMANCE (NOMINAL DESIGN CONDITIONS)
COOLING CAPACITY
22.68
TONS
ALTITUDE
SEA LEVEL
COOLANT SUPPLY
TEMPERATURE
50
°F
COMPRESSOR POWER
16970
WATTS
CONDENSER INLET WATER
TEMP
85
°F
EER
16.04 BTU/WATT
COOLANT
WATER
CONDENSER WATER FLOW
68
GPM
COOLANT FLOW
54
GPM
SOUND POWER LEVEL
74
dBA
UNIT PRESSURE DROP
7
PSID
SOUND PRESS LEVEL @ 1
METER
dBA
OPERATING PARAMETERS
COOLANT SUPPLY
TEMPERATURE
20-80
°F
COOLANT FLOW
24-96
GPM
CONDENSER INLET WATER
TEMP
50-90
°F
MINIMUM LOAD
4.54
TONS
SPECIFICATIONS
COMPRESSOR
SCROLL
FRAME
GALVANIZED STEEL
EVAPORATOR
BRAZED PLATE
COOLANT CIRCUIT
NON-FERROUS
CONDENSER
SHELL &
TUBE
REFRIGERANT
22 LBS R-410A
EVAPORATOR FILTER
20 MESH
WEIGHT (OPERATING)
1660.95
LBS
POWER
460V/3PH/60HZ
WEIGHT (SHIPPING)
940.95
LBS
CONTROL CIRCUIT
24/120
VAC
ELECTRICAL ENCLOSURE
NEMA 4/12
COMPRESSOR RATED LOAD
AMPS
(2) @ 17.9 AMPS EACH
CONTROL
MICROPROCESSOR