3 specifications, Remote air-cooled central chillers – Sterlco GC Series Central Chiller User Manual

Page 54

Advertising
background image

GC Series Central Chillers

Chapter 7: Appendix

54 of 79

7-3 Specifications

Remote Air-Cooled Central Chillers

Nominal operating parameters for remote air-cooled models are 50ºF (10ºC) leaving water temperature at
2.4 gpm per ton (9.1 lpm per 3.517 kW) with 95ºF (35ºC) ambient air. For 50 Hz applications, multiply
capacity by 0.83. Nominal 60 Hz capacity flow rate must be maintained.

20 TON (GCRC-70)

PERFORMANCE (NOMINAL DESIGN CONDITIONS)

COOLING CAPACITY

20.16

TONS

ALTITUDE

SEA LEVEL

COOLANT SUPPLY
TEMPERATURE

50

°F

COMPRESSOR POWER

20048

WATTS

AMBIENT AIR TEMPERATURE

95

°F

EER

12.07 BTU/WATT

COOLANT

WATER

COOLANT FLOW

48

GPM

SOUND POWER LEVEL

89

dBA

UNIT PRESSURE DROP

7

PSID

SOUND PRESS LEVEL @ 1
METER

dBA

OPERATING PARAMETERS

COOLANT SUPPLY
TEMPERATURE

20-80

°F

COOLANT FLOW

24-96

GPM

AMBIENT AIR TEMPERATURE

60-115

°F

MINIMUM LOAD

4.03

TONS

SPECIFICATIONS

COMPRESSOR

SCROLL

FRAME

GALVANIZED STEEL

EVAPORATOR

BRAZED PLATE

COOLANT CIRCUIT

NON-FERROUS

EVAPORATOR FILTER

20 MESH

WEIGHT (OPERATING)

1296.8

LBS

POWER

460V/3PH/60HZ

WEIGHT (SHIPPING)

626.8

LBS

CONTROL CIRCUIT

24/120

VAC

ELECTRICAL ENCLOSURE

NEMA 4/12

COMPRESSOR RATED LOAD
AMPS

(2) @ 17.9 AMPS EACH

CONTROL

MICROPROCESSOR

20 TON (GCRC-70)

SPECIFICATIONS

AMBIENT TEMPERATURE
RANGE

-20 to 115

°F

SOUND POWER LEVEL

89

dBA

CONDENSER AIR FLOW

16916

CFM

SOUND PRESS LEVEL @ 1
METER

dBA

CONDENSER

ALUMINUM

FRAME

GALVANIZED STEEL

CONDENSER FANS

(2) 32 INCH AXIAL

PANELS

POWDER COATED
STEEL

CONDENSER FAN MOTOR

(2) 1 HP OAO, 1140 RPM , 2.1
FLA

WEIGHT (SHIPPING)

692

LBS

POWER

460V/3PH/60HZ

Advertising