Sterlco GC Series Central Chiller User Manual

Page 47

Advertising
background image

GC Series Central Chillers

Chapter 6: Troubleshooting

47 of 79

Problem

Possible cause

Solution

Compressor not operating
efficiently.

Call service.

Unit under-sized for application.

Call sales rep

Troubleshooting Warnings and Faults from the PLC

Controller Alarm

Possible Cause

Solution

Compressor Fault

Compressor Internal Overload Fault Allow time to cool and reset, then

check for high/low voltage. It must be
within ±10% of the nameplate rating.

Compressor Motor Circuit
Protector Open

Verify switch is in the “ON” position
Verify amp value is at its highest
Check for high/low line voltage. It
must be within ±10% of the nameplate
rating

Discharge Pressure Sensor Failure

Packard connector separated from
sensor

Reconnect wire connector to sensor

Input to PLC is missing

Verify wiring at PLC.

Faulty sensor cable

Replace cable

Faulty sensor

Replace sensor

VFD Fault

See Troubleshooting the ABB

Variable Speed Drive below

See Troubleshooting the ABB Variable

Speed Drive below

Fan VFD fuses blown

Replace fuses

Fan motor overload tripped

Reset overload/verify overload setting

Input to PLC is missing

Verify wiring at digital input ID4 at
PLC

High Discharge Pressure Fault
(Discharge pressure has exceeded

fault setpoint)

See VFD Fault above

See VFD Fault above

Condenser inlet temperature too

high

Contact ACS Group Aftermarket

Service for assistance

Refrigerant overcharge

Contact refrigeration technician about
removing refrigerant as needed

Dirty condenser

Clean condenser

Fan motor failure

Verify fan motor operation, replace as
needed

No analog output from PLC

Verify wiring at analog output J4 per

print.
Verify VFD AI Type selector switch is
in the U position.

High Discharge Pressure Switch
(Discharge pressure has exceeded
switch 575 psig setting)

Input to PLC is missing

Verify wiring at digital input ID2 at
PLC

VFD Fault

See VFD Fault above

Condenser inlet temperature too

high

Contact ACS Group Aftermarket

Service for assistance

Refrigerant overcharge

Contact refrigeration technician about
removing refrigerant as needed

Dirty condenser

Clean condenser

Fan motor failure

Verify fan motor operation, replace as
needed

No analog output from PLC

Verify wiring at analog output J4 per

print.
Verify VFD AI Type selector switch is
in the U position.

High Suction Pressure Fault
(Suction pressure has exceeded
fault setpoint)

Load may be too high for chiller

Contact your sales representative for
assistance.

Low Discharge Pressure Fault
(Discharge pressure has fallen
below fault setpoint)

Condenser inlet temperature too
low

Contact ACS Group Aftermarket
Service for assistance

VFD fault

See VFD Fault above

Condenser water regulating valve

open

Verify analog output at Y1