GC Series Central Chillers

Chapter 7: Appendix

64 of 79

7-4 Flow and Pressure Considerations

Pure Water at >40°F (4.4°C)

GCXC-70

GCXC-90

GCXC-140

GCXC-175

0.5X Nominal

24

1.7

30

1.8

36

1.7

48

1.8

1.0X Nominal

48

6.1

60

6.5

72

6.1

96

6.4

2.0X Nominal

96

21.9

120

23.5

144

22.1

192

23.6

GCXC-210

0.5X Nominal

72

1.7

1.0X Nominal

144

6.2

2.0X Nominal

288

22.7

Calculating Chiller Nominal Flow and Pressure to Process

Flow rate: Obtain the flow reading from the appropriate pump curve.

Pressure: Obtain a corresponding pressure reading from the pump curve you selected,

then subtract the one-pump pressure drop listed in the above table using the
appropriate chiller hp and flow rate.