Master Programming Mode

CAUTION: Before entering Master Programming, please contact your local professional water dealer.

2. Valve Type (Display Code VT)

Press the Extra Cycle button. Use this display to set the Valve Type. The Valve Type setting specifies the type of

cycle that the valve follows during regeneration. Note that some valve types require that the valve be built with

specific subcomponents. Ensure the valve is configured properly before changing the Valve Type setting. This

option setting is identified by “VT” in the upper left hand corner of the screen. There are 5 possible settings:

Abbreviation

Parameter

St1b

Standard Downflow/Upflow, Single Backwash

St2b

Standard Downflow/Upflow, Double Backwash

Fltr

Filter

UFbF

Upflow Brine First

Othr

Other

.
.
.
.
.
.

3. Control Type (Display Code CT)

Press the Extra Cycle button. Use this display to set the Control Type. This specifies how the control determines

when to trigger a regeneration. For details on how the various options function, refer to the “Timer Operation”

section of this service manual. This option setting is identified by “CT” in the upper left hand corner of the screen.

There are four possible settings:

Meter Delayed:

Fd

Meter Immediate:

FI

Time Clock:

tc

Day of Week:

dAY

4. Number of Tanks (Display Code NT)

Press the Extra Cycle button. Use this display to set the Number of Tanks in your system. This option setting is

identified by “NT” in the upper left hand corner of the screen. There are two possible settings:

Single Tank System:

1

Two-Tank System: