UPS Upgrade

Adding a UPS

The following UPS systems can be added to the HP NAS 8000 solution after

the time of purchase. The specific model of UPS recommended is customized

each region:

■

American Power Conversion (APC) Symmetra RM (8U)

■

American Power Conversion (APC) Symmetra RM (15U)

■

American Power Conversion (APC) Symmetra

To install the UPS on the HP NAS 8000 solution, follow these steps:

1

Follow the instructions that came with the UPS for power requirements.

2

Power down all of the solution components in the following sequence

before installing the UPS:

—

NAS server(s)

—

Quorum server (for high-availability configurations)

—

Array

—

FC switch (for high-availability configurations)

—

Library

3

Install the UPS in the bottom of the rack to avoid having a top-heavy rack

and to eliminate the risk of tip over.

4

Connect the communications port on the UPS to the server's COM1 serial

port.

5

Plug components into PDU on UPS.

6

Connect power to UPS.

■

If you are installing the Symmetra RM UPS:

—

If the planned power load is less than or equal to 5 kVA, plug the line

into an appropriate outlet.

—

If the planned power load is greater than 5 kVA, a qualified electrician

must hard wire the input power.

■

If you are installing the Symmetra UPS:

—

Regardless of the power load, a qualified electrician must hard wire

the input power.