system must be earthed elsewhere.

The DC supply source is to be located within the same premises as the equipment.

Switching or disconnecting devices must not be in the earthed circuit conductor between the

DC source and the point of connection of the earthing electrode conductor.

CAUTION:

To reduce the risk of electric shock or energy hazards:

This equipment must be installed by trained service personnel, as defined by the NEC and IEC

60950-1, Second Edition, the standard for Safety of Information Technology Equipment.

Connect the equipment to a reliably grounded SELV source. An SELV source is a secondary

circuit that is designed so normal and single fault conditions do not cause the voltages to
exceed a safe level (60 V DC).

The branch circuit overcurrent protection must be rated 24 A.

Power supply calculations

For power supply specifications and calculators to determine electrical and heat loading for the server, refer

to the HP Enterprise Configurator website (

http://h30099.www3.hp.com/configurator/

).